Parameter
Nom.Cross-section Area | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | mm | km/kg | Ω/km | A | A |
3×35 | 50.0 | 4055 | 0.524 | 172 | 154 |
3×50 | 53.0 | 4770 | 0.387 | 205 | 181 |
3×70 | 57.5 | 5695 | 0.268 | 253 | 220 |
3×95 | 61.5 | 6755 | 0.193 | 307 | 263 |
3×120 | 65.0 | 7675 | 0.153 | 352 | 298 |
3×150 | 68.0 | 9215 | 0.124 | 397 | 332 |
3×185 | 72.0 | 10605 | 0.0991 | 453 | 374 |
3×240 | 78.5 | 13330 | 0.0754 | 529 | 431 |
3×300 | 86.0 | 15880 | 0.0601 | 599 | 482 |
N2XSEYBY 3.6/6kV
Nom.Cross-section Area | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | mm | km/kg | Ω/km | A | A |
3×35 | 54.5 | 4,495 | 0.524 | 172 | 154 |
3×50 | 57.5 | 5,265 | 0.387 | 205 | 181 |
3×70 | 62 | 6,225 | 0.268 | 253 | 220 |
3×95 | 66 | 7,345 | 0.193 | 307 | 263 |
3×120 | 69.5 | 8.295 | 0.153 | 352 | 298 |
3×150 | 72.5 | 9,835 | 0.124 | 397 | 332 |
3×185 | 76 | 11,255 | 0.0991 | 453 | 374 |
3×240 | 83.5 | 14,030 | 0.0754 | 529 | 431 |
3×300 | 89 | 16,435 | 0.0601 | 599 | 482 |
N2XSEYBY 6/10kV
Nom.Cross-section Area | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | mm | km/kg | Ω/km | A | A |
3×35 | 60 | 5,165 | 0.524 | 172 | 154 |
3×50 | 63 | 5,940 | 0.387 | 205 | 181 |
3×70 | 67.5 | 6,940 | 0.268 | 253 | 220 |
3×95 | 71.5 | 8,075 | 0.193 | 307 | 263 |
3×120 | 75 | 9,055 | 0.153 | 352 | 298 |
3×150 | 78 | 10,665 | 0.124 | 397 | 332 |
3×185 | 82 | 12,120 | 0.0991 | 453 | 374 |
3×240 | 88 | 14,955 | 0.0754 | 529 | 431 |
3×300 | 94.5 | 17,470 | 0.0601 | 599 | 482 |
N2XSEYBY 8.7/15kV
Nom.Cross-section Area | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | mm | km/kg | Ω/km | A | A |
3×35 | 65 | 5,715 | 0.524 | 172 | 154 |
3×50 | 68 | 6,545 | 0.387 | 205 | 181 |
3×70 | 72.5 | 7,615 | 0.268 | 253 | 220 |
3×95 | 76 | 8,750 | 0.193 | 307 | 263 |
3×120 | 79.5 | 9,795 | 0.153 | 352 | 298 |
3×150 | 84.5 | 12,145 | 0.124 | 397 | 332 |
3×185 | 87.5 | 13,620 | 0.0991 | 453 | 374 |
3×240 | 92.5 | 15,805 | 0.0754 | 529 | 431 |
3×300 | 99.5 | 18,375 | 0.0601 | 599 | 482 |
N2XSEYBY 12/20kV
Cable Structure
● Conductor:Compact stranded copper conductor,CI.2 as per IEC 60228
● Conductor Screen: Semi-conductor
● Insulation:XLPE rated at 90°C
● Conducting Water Blocking Layer:Semi-conductive WBT
● ID Tape:Red/Yellow/Black
● Metallic Screen:Copper Wire Screen
● Metallic Screen:Copper Tape Screen
● Separator/Water Blocking Layer:Non-Conductive WBT
● Separation Sheath(for armoured cable):PVC inner Sheath(Fully extruded)
● Armoring:Double stainless steel tape-1 core
Double galvanized steel tape-3 cores
●Sheath:PVC orFR-PVC type ST2/ST8 to IEC 60502,black
Code Designation
YJ:XLPE insulation
V:PVC sheath
22:Double galvanized steel wire armoring-3 cores
62:Double stainless steel tape armoring-1 core
ZR:Flame resistant
European Union:N2XSEYBY/NA2XSEYBY
Application
They are suitable for installation mostly in power supply stations, indoors and in cable ducts,outdoors,underground and in water as well as for installation on cable trays for industries,switchboards and power stations.
Standard
International:IEC 60502,EC60228,(IEC60332-3forZR-YJV22,ZR-YJV62only)
China:GB/T12706,(GB/T18380-3forZR-YJV22,ZR-YJV62only)
European standard:DIN VDE0276-620,HD620S2,IEC/EN 60228,IEC/EN 60502-2
Flame Retardant according to IEC/EN 60332-1-2
Indonesian Standard:Conductor:SNI IEC 60228/Insulation:SNI IEC 60502-2
Other standards such as BS,DIN and ICEA upon request
Technical Data
Rated voltage:3.6/6KV6/10KV 8.7/15KV 12/20KV
Maximum Conductor Temperature:under normal (90℃),emergency(130℃)or short circuit no more than 5s (250℃)conditions.
Min.Ambient Temp.-20°℃,Installation Temp.0℃
Min.Bending Radius:15×cable O.D for single core
12×cable O.D for multi core
Certificates
CE,RoHS,CCC,KEMA and more others at request