Parametre
Nom. Kesit Alanı | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | mm | km/kg | Ω/km | A | A |
3×35 | 50.0 | 4055 | 0.524 | 172 | 154 |
3×50 | 53.0 | 4770 | 0.387 | 205 | 181 |
3×70 | 57.5 | 5695 | 0.268 | 253 | 220 |
3×95 | 61.5 | 6755 | 0.193 | 307 | 263 |
3×120 | 65.0 | 7675 | 0.153 | 352 | 298 |
3×150 | 68.0 | 9215 | 0.124 | 397 | 332 |
3×185 | 72.0 | 10605 | 0.0991 | 453 | 374 |
3×240 | 78.5 | 13330 | 0.0754 | 529 | 431 |
3×300 | 86.0 | 15880 | 0.0601 | 599 | 482 |
N2XSEYBY 3.6/6kV
Nom. Kesit Alanı | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | mm | km/kg | Ω/km | A | A |
3×35 | 54.5 | 4,495 | 0.524 | 172 | 154 |
3×50 | 57.5 | 5,265 | 0.387 | 205 | 181 |
3×70 | 62 | 6,225 | 0.268 | 253 | 220 |
3×95 | 66 | 7,345 | 0.193 | 307 | 263 |
3×120 | 69.5 | 8.295 | 0.153 | 352 | 298 |
3×150 | 72.5 | 9,835 | 0.124 | 397 | 332 |
3×185 | 76 | 11,255 | 0.0991 | 453 | 374 |
3×240 | 83.5 | 14,030 | 0.0754 | 529 | 431 |
3×300 | 89 | 16,435 | 0.0601 | 599 | 482 |
N2XSEYBY 6/10kV
Nom. Kesit Alanı | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | mm | km/kg | Ω/km | A | A |
3×35 | 60 | 5,165 | 0.524 | 172 | 154 |
3×50 | 63 | 5,940 | 0.387 | 205 | 181 |
3×70 | 67.5 | 6,940 | 0.268 | 253 | 220 |
3×95 | 71.5 | 8,075 | 0.193 | 307 | 263 |
3×120 | 75 | 9,055 | 0.153 | 352 | 298 |
3×150 | 78 | 10,665 | 0.124 | 397 | 332 |
3×185 | 82 | 12,120 | 0.0991 | 453 | 374 |
3×240 | 88 | 14,955 | 0.0754 | 529 | 431 |
3×300 | 94.5 | 17,470 | 0.0601 | 599 | 482 |
N2XSEYBY 8.7/15kV
Nom. Kesit Alanı | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | mm | km/kg | Ω/km | A | A |
3×35 | 65 | 5,715 | 0.524 | 172 | 154 |
3×50 | 68 | 6,545 | 0.387 | 205 | 181 |
3×70 | 72.5 | 7,615 | 0.268 | 253 | 220 |
3×95 | 76 | 8,750 | 0.193 | 307 | 263 |
3×120 | 79.5 | 9,795 | 0.153 | 352 | 298 |
3×150 | 84.5 | 12,145 | 0.124 | 397 | 332 |
3×185 | 87.5 | 13,620 | 0.0991 | 453 | 374 |
3×240 | 92.5 | 15,805 | 0.0754 | 529 | 431 |
3×300 | 99.5 | 18,375 | 0.0601 | 599 | 482 |
N2XSEYBY 12/20kV
Kablo Yapısı
● Conductor:Compact stranded copper conductor,CI.2 as per IEC 60228
● İletken Ekranı: Yarı iletken
● Insulation:XLPE rated at 90°C
● Conducting Water Blocking Layer:Semi-conductive WBT
● ID Tape:Red/Yellow/Black
● Metallic Screen:Copper Wire Screen
● Metallic Screen:Copper Tape Screen
● Separator/Water Blocking Layer:Non-Conductive WBT
● Separation Sheath(for armoured cable):PVC inner Sheath(Fully extruded)
● Armoring:Double stainless steel tape-1 core
Double galvanized steel tape-3 cores
●Sheath:PVC orFR-PVC type ST2/ST8 to IEC 60502,black
Kod Tanımı
YJ:XLPE izolasyonu
V:PVC kılıf
22:Çift galvanizli çelik tel zırhlama-3 damar
62:Çift paslanmaz çelik bant zırhlama-1 çekirdek
ZR:Aleve dayanıklı
European Union:N2XSEYBY/NA2XSEYBY
Başvuru
They are suitable for installation mostly in power supply stations, indoors and in cable ducts,outdoors,underground and in water as well as for installation on cable trays for industries,switchboards and power stations.
Standart
International:IEC 60502,EC60228,(IEC60332-3forZR-YJV22,ZR-YJV62only)
China:GB/T12706,(GB/T18380-3forZR-YJV22,ZR-YJV62only)
European standard:DIN VDE0276-620,HD620S2,IEC/EN 60228,IEC/EN 60502-2
Flame Retardant according to IEC/EN 60332-1-2
Indonesian Standard:Conductor:SNI IEC 60228/Insulation:SNI IEC 60502-2
Talep üzerine BS,DIN ve ICEA gibi diğer standartlar
Teknik veri
Rated voltage:3.6/6KV6/10KV 8.7/15KV 12/20KV
Maksimum İletken Sıcaklığı: normal (90°C), acil durum (130°C) veya kısa devre koşullarında 5 saniyeden (250°C) fazla olmamalıdır.
Min.Ambient Temp.-20°℃,Installation Temp.0℃
Min.Büküm Yarıçapı:Tek damar için 15×kablo dış çapı
Çok çekirdekli için 12×kablo dış çapı
Sertifikalar
CE,RoHS,CCC,KEMA ve daha fazlası istek üzerine