Parameter
Nom.Tvärsnittsarea | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | mm | km/kg | Ω/km | A | A |
3×35 | 50.0 | 4055 | 0.524 | 172 | 154 |
3×50 | 53.0 | 4770 | 0.387 | 205 | 181 |
3×70 | 57.5 | 5695 | 0.268 | 253 | 220 |
3×95 | 61.5 | 6755 | 0.193 | 307 | 263 |
3×120 | 65.0 | 7675 | 0.153 | 352 | 298 |
3×150 | 68.0 | 9215 | 0.124 | 397 | 332 |
3×185 | 72.0 | 10605 | 0.0991 | 453 | 374 |
3×240 | 78.5 | 13330 | 0.0754 | 529 | 431 |
3×300 | 86.0 | 15880 | 0.0601 | 599 | 482 |
N2XSEYBY 3.6/6kV
Nom.Tvärsnittsarea | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | mm | km/kg | Ω/km | A | A |
3×35 | 54.5 | 4,495 | 0.524 | 172 | 154 |
3×50 | 57.5 | 5,265 | 0.387 | 205 | 181 |
3×70 | 62 | 6,225 | 0.268 | 253 | 220 |
3×95 | 66 | 7,345 | 0.193 | 307 | 263 |
3×120 | 69.5 | 8.295 | 0.153 | 352 | 298 |
3×150 | 72.5 | 9,835 | 0.124 | 397 | 332 |
3×185 | 76 | 11,255 | 0.0991 | 453 | 374 |
3×240 | 83.5 | 14,030 | 0.0754 | 529 | 431 |
3×300 | 89 | 16,435 | 0.0601 | 599 | 482 |
N2XSEYBY 6/10kV
Nom.Tvärsnittsarea | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | mm | km/kg | Ω/km | A | A |
3×35 | 60 | 5,165 | 0.524 | 172 | 154 |
3×50 | 63 | 5,940 | 0.387 | 205 | 181 |
3×70 | 67.5 | 6,940 | 0.268 | 253 | 220 |
3×95 | 71.5 | 8,075 | 0.193 | 307 | 263 |
3×120 | 75 | 9,055 | 0.153 | 352 | 298 |
3×150 | 78 | 10,665 | 0.124 | 397 | 332 |
3×185 | 82 | 12,120 | 0.0991 | 453 | 374 |
3×240 | 88 | 14,955 | 0.0754 | 529 | 431 |
3×300 | 94.5 | 17,470 | 0.0601 | 599 | 482 |
N2XSEYBY 8.7/15kV
Nom.Tvärsnittsarea | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | mm | km/kg | Ω/km | A | A |
3×35 | 65 | 5,715 | 0.524 | 172 | 154 |
3×50 | 68 | 6,545 | 0.387 | 205 | 181 |
3×70 | 72.5 | 7,615 | 0.268 | 253 | 220 |
3×95 | 76 | 8,750 | 0.193 | 307 | 263 |
3×120 | 79.5 | 9,795 | 0.153 | 352 | 298 |
3×150 | 84.5 | 12,145 | 0.124 | 397 | 332 |
3×185 | 87.5 | 13,620 | 0.0991 | 453 | 374 |
3×240 | 92.5 | 15,805 | 0.0754 | 529 | 431 |
3×300 | 99.5 | 18,375 | 0.0601 | 599 | 482 |
N2XSEYBY 12/20kV
Kabelstruktur
● Conductor:Compact stranded copper conductor,CI.2 as per IEC 60228
● Ledarskärm: Halvledare
● Insulation:XLPE rated at 90°C
● Conducting Water Blocking Layer:Semi-conductive WBT
● ID Tape:Red/Yellow/Black
● Metallic Screen:Copper Wire Screen
● Metallic Screen:Copper Tape Screen
● Separator/Water Blocking Layer:Non-Conductive WBT
● Separation Sheath(for armoured cable):PVC inner Sheath(Fully extruded)
● Armoring:Double stainless steel tape-1 core
Double galvanized steel tape-3 cores
●Sheath:PVC orFR-PVC type ST2/ST8 to IEC 60502,black
Kodbeteckning
YJ:XLPE-isolering
V: PVC-mantel
22:Dubbel galvaniserad ståltrådsarmering-3 kärnor
62:Dubbel rostfri tejp armering-1 kärna
ZR: Flamsäker
European Union:N2XSEYBY/NA2XSEYBY
Ansökan
They are suitable for installation mostly in power supply stations, indoors and in cable ducts,outdoors,underground and in water as well as for installation on cable trays for industries,switchboards and power stations.
Standard
International:IEC 60502,EC60228,(IEC60332-3forZR-YJV22,ZR-YJV62only)
China:GB/T12706,(GB/T18380-3forZR-YJV22,ZR-YJV62only)
European standard:DIN VDE0276-620,HD620S2,IEC/EN 60228,IEC/EN 60502-2
Flame Retardant according to IEC/EN 60332-1-2
Indonesian Standard:Conductor:SNI IEC 60228/Insulation:SNI IEC 60502-2
Andra standarder som BS,DIN och ICEA på begäran
Teknisk data
Rated voltage:3.6/6KV6/10KV 8.7/15KV 12/20KV
Maximal ledartemperatur: under normala (90 ℃), nödsituationer (130 ℃) eller kortslutning inte mer än 5 s (250 ℃) förhållanden.
Min.Ambient Temp.-20°℃,Installation Temp.0℃
Min. Böjningsradie: 15×kabel OD för enkelkärna
12×kabel OD för multi-core
Certifikat
CE, RoHS, CCC, KEMA och fler andra på begäran