પરિમાણ
Nom.Cross-section Area | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | મીમી | km/kg | Ω/કિમી | A | A |
3×35 | 50.0 | 4055 | 0.524 | 172 | 154 |
3×50 | 53.0 | 4770 | 0.387 | 205 | 181 |
3×70 | 57.5 | 5695 | 0.268 | 253 | 220 |
3×95 | 61.5 | 6755 | 0.193 | 307 | 263 |
3×120 | 65.0 | 7675 | 0.153 | 352 | 298 |
3×150 | 68.0 | 9215 | 0.124 | 397 | 332 |
3×185 | 72.0 | 10605 | 0.0991 | 453 | 374 |
3×240 | 78.5 | 13330 | 0.0754 | 529 | 431 |
3×300 | 86.0 | 15880 | 0.0601 | 599 | 482 |
N2XSEYBY 3.6/6kV
Nom.Cross-section Area | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | મીમી | km/kg | Ω/કિમી | A | A |
3×35 | 54.5 | 4,495 | 0.524 | 172 | 154 |
3×50 | 57.5 | 5,265 | 0.387 | 205 | 181 |
3×70 | 62 | 6,225 | 0.268 | 253 | 220 |
3×95 | 66 | 7,345 | 0.193 | 307 | 263 |
3×120 | 69.5 | 8.295 | 0.153 | 352 | 298 |
3×150 | 72.5 | 9,835 | 0.124 | 397 | 332 |
3×185 | 76 | 11,255 | 0.0991 | 453 | 374 |
3×240 | 83.5 | 14,030 | 0.0754 | 529 | 431 |
3×300 | 89 | 16,435 | 0.0601 | 599 | 482 |
N2XSEYBY 6/10kV
Nom.Cross-section Area | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | મીમી | km/kg | Ω/કિમી | A | A |
3×35 | 60 | 5,165 | 0.524 | 172 | 154 |
3×50 | 63 | 5,940 | 0.387 | 205 | 181 |
3×70 | 67.5 | 6,940 | 0.268 | 253 | 220 |
3×95 | 71.5 | 8,075 | 0.193 | 307 | 263 |
3×120 | 75 | 9,055 | 0.153 | 352 | 298 |
3×150 | 78 | 10,665 | 0.124 | 397 | 332 |
3×185 | 82 | 12,120 | 0.0991 | 453 | 374 |
3×240 | 88 | 14,955 | 0.0754 | 529 | 431 |
3×300 | 94.5 | 17,470 | 0.0601 | 599 | 482 |
N2XSEYBY 8.7/15kV
Nom.Cross-section Area | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | મીમી | km/kg | Ω/કિમી | A | A |
3×35 | 65 | 5,715 | 0.524 | 172 | 154 |
3×50 | 68 | 6,545 | 0.387 | 205 | 181 |
3×70 | 72.5 | 7,615 | 0.268 | 253 | 220 |
3×95 | 76 | 8,750 | 0.193 | 307 | 263 |
3×120 | 79.5 | 9,795 | 0.153 | 352 | 298 |
3×150 | 84.5 | 12,145 | 0.124 | 397 | 332 |
3×185 | 87.5 | 13,620 | 0.0991 | 453 | 374 |
3×240 | 92.5 | 15,805 | 0.0754 | 529 | 431 |
3×300 | 99.5 | 18,375 | 0.0601 | 599 | 482 |
N2XSEYBY 12/20kV
કેબલ માળખું
● Conductor:Compact stranded copper conductor,CI.2 as per IEC 60228
● કંડક્ટર સ્ક્રીન: સેમી-કન્ડક્ટર
● Insulation:XLPE rated at 90°C
● Conducting Water Blocking Layer:Semi-conductive WBT
● ID Tape:Red/Yellow/Black
● Metallic Screen:Copper Wire Screen
● Metallic Screen:Copper Tape Screen
● Separator/Water Blocking Layer:Non-Conductive WBT
● Separation Sheath(for armoured cable):PVC inner Sheath(Fully extruded)
● Armoring:Double stainless steel tape-1 core
Double galvanized steel tape-3 cores
●Sheath:PVC orFR-PVC type ST2/ST8 to IEC 60502,black
કોડ હોદ્દો
YJ:XLPE ઇન્સ્યુલેશન
વી: પીવીસી આવરણ
22:ડબલ ગેલ્વેનાઈઝ્ડ સ્ટીલ વાયર આર્મિંગ-3 કોરો
62:ડબલ સ્ટેનલેસ સ્ટીલ ટેપ આર્મરિંગ-1 કોર
ZR: જ્યોત પ્રતિરોધક
European Union:N2XSEYBY/NA2XSEYBY
અરજી
They are suitable for installation mostly in power supply stations, indoors and in cable ducts,outdoors,underground and in water as well as for installation on cable trays for industries,switchboards and power stations.
ધોરણ
International:IEC 60502,EC60228,(IEC60332-3forZR-YJV22,ZR-YJV62only)
China:GB/T12706,(GB/T18380-3forZR-YJV22,ZR-YJV62only)
European standard:DIN VDE0276-620,HD620S2,IEC/EN 60228,IEC/EN 60502-2
Flame Retardant according to IEC/EN 60332-1-2
Indonesian Standard:Conductor:SNI IEC 60228/Insulation:SNI IEC 60502-2
વિનંતી પર BS,DIN અને ICEA જેવા અન્ય ધોરણો
ટેકનિકલ ડેટા
Rated voltage:3.6/6KV6/10KV 8.7/15KV 12/20KV
મહત્તમ કંડક્ટર તાપમાન:સામાન્ય (90℃), કટોકટી (130℃) અથવા શોર્ટ સર્કિટ 5s (250℃)થી વધુ સ્થિતિઓ હેઠળ નહીં.
Min.Ambient Temp.-20°℃,Installation Temp.0℃
લઘુત્તમ બેન્ડિંગ ત્રિજ્યા: સિંગલ કોર માટે 15×કેબલ OD
મલ્ટી કોર માટે 12×કેબલ OD
પ્રમાણપત્રો
વિનંતી પર CE,RoHS,CCC,KEMA અને વધુ અન્ય