Paramèt
Nom.Cross-section Area | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | mm | km/kg | Ω/km | A | A |
3×35 | 50.0 | 4055 | 0.524 | 172 | 154 |
3×50 | 53.0 | 4770 | 0.387 | 205 | 181 |
3×70 | 57.5 | 5695 | 0.268 | 253 | 220 |
3×95 | 61.5 | 6755 | 0.193 | 307 | 263 |
3×120 | 65.0 | 7675 | 0.153 | 352 | 298 |
3×150 | 68.0 | 9215 | 0.124 | 397 | 332 |
3×185 | 72.0 | 10605 | 0.0991 | 453 | 374 |
3×240 | 78.5 | 13330 | 0.0754 | 529 | 431 |
3×300 | 86.0 | 15880 | 0.0601 | 599 | 482 |
N2XSEYBY 3.6/6kV
Nom.Cross-section Area | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | mm | km/kg | Ω/km | A | A |
3×35 | 54.5 | 4,495 | 0.524 | 172 | 154 |
3×50 | 57.5 | 5,265 | 0.387 | 205 | 181 |
3×70 | 62 | 6,225 | 0.268 | 253 | 220 |
3×95 | 66 | 7,345 | 0.193 | 307 | 263 |
3×120 | 69.5 | 8.295 | 0.153 | 352 | 298 |
3×150 | 72.5 | 9,835 | 0.124 | 397 | 332 |
3×185 | 76 | 11,255 | 0.0991 | 453 | 374 |
3×240 | 83.5 | 14,030 | 0.0754 | 529 | 431 |
3×300 | 89 | 16,435 | 0.0601 | 599 | 482 |
N2XSEYBY 6/10kV
Nom.Cross-section Area | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | mm | km/kg | Ω/km | A | A |
3×35 | 60 | 5,165 | 0.524 | 172 | 154 |
3×50 | 63 | 5,940 | 0.387 | 205 | 181 |
3×70 | 67.5 | 6,940 | 0.268 | 253 | 220 |
3×95 | 71.5 | 8,075 | 0.193 | 307 | 263 |
3×120 | 75 | 9,055 | 0.153 | 352 | 298 |
3×150 | 78 | 10,665 | 0.124 | 397 | 332 |
3×185 | 82 | 12,120 | 0.0991 | 453 | 374 |
3×240 | 88 | 14,955 | 0.0754 | 529 | 431 |
3×300 | 94.5 | 17,470 | 0.0601 | 599 | 482 |
N2XSEYBY 8.7/15kV
Nom.Cross-section Area | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | mm | km/kg | Ω/km | A | A |
3×35 | 65 | 5,715 | 0.524 | 172 | 154 |
3×50 | 68 | 6,545 | 0.387 | 205 | 181 |
3×70 | 72.5 | 7,615 | 0.268 | 253 | 220 |
3×95 | 76 | 8,750 | 0.193 | 307 | 263 |
3×120 | 79.5 | 9,795 | 0.153 | 352 | 298 |
3×150 | 84.5 | 12,145 | 0.124 | 397 | 332 |
3×185 | 87.5 | 13,620 | 0.0991 | 453 | 374 |
3×240 | 92.5 | 15,805 | 0.0754 | 529 | 431 |
3×300 | 99.5 | 18,375 | 0.0601 | 599 | 482 |
N2XSEYBY 12/20kV
Estrikti kab
● Conductor:Compact stranded copper conductor,CI.2 as per IEC 60228
● Kondiktè ekran: Semi-kondiktè
● Insulation:XLPE rated at 90°C
● Conducting Water Blocking Layer:Semi-conductive WBT
● ID Tape:Red/Yellow/Black
● Metallic Screen:Copper Wire Screen
● Metallic Screen:Copper Tape Screen
● Separator/Water Blocking Layer:Non-Conductive WBT
● Separation Sheath(for armoured cable):PVC inner Sheath(Fully extruded)
● Armoring:Double stainless steel tape-1 core
Double galvanized steel tape-3 cores
●Sheath:PVC orFR-PVC type ST2/ST8 to IEC 60502,black
Deziyasyon Kòd
YJ: XLPE izolasyon
V: PVC djenn
22: doub fil asye galvanised armoring-3 nwayo
62: doub asye pur kasèt blende-1 nwayo
ZR: Flanm dife rezistan
European Union:N2XSEYBY/NA2XSEYBY
Aplikasyon
They are suitable for installation mostly in power supply stations, indoors and in cable ducts,outdoors,underground and in water as well as for installation on cable trays for industries,switchboards and power stations.
Estanda
International:IEC 60502,EC60228,(IEC60332-3forZR-YJV22,ZR-YJV62only)
China:GB/T12706,(GB/T18380-3forZR-YJV22,ZR-YJV62only)
European standard:DIN VDE0276-620,HD620S2,IEC/EN 60228,IEC/EN 60502-2
Flame Retardant according to IEC/EN 60332-1-2
Indonesian Standard:Conductor:SNI IEC 60228/Insulation:SNI IEC 60502-2
Lòt estanda tankou BS, DIN ak ICEA sou demann
Done teknik
Rated voltage:3.6/6KV6/10KV 8.7/15KV 12/20KV
Tanperati maksimòm kondiktè: nan kondisyon nòmal (90 ℃), ijans (130 ℃) oswa kous kout pa plis pase 5s (250 ℃).
Min.Ambient Temp.-20°℃,Installation Temp.0℃
Min.Bending Radius: 15 × kab OD pou nwayo sèl
12 × kab OD pou nwayo milti
Sètifika
CE, RoHS, CCC, KEMA ak plis lòt moun sou demann