Paramita
Nom.Cross-apakan Area | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | mm | km/kg | Ω/km | A | A |
3×35 | 50.0 | 4355 | 0.524 | 172 | 154 |
3×50 | 53.0 | 5095 | 0.387 | 205 | 181 |
3×70 | 57.5 | 6045 | 0.268 | 253 | 220 |
3×95 | 61.5 | 7165 | 0.193 | 307 | 263 |
3×120 | 65.0 | 8105 | 0.153 | 352 | 298 |
3×150 | 68.0 | 9645 | 0.124 | 397 | 332 |
3×185 | 72.0 | 11055 | 0.0991 | 453 | 374 |
3×240 | 77.0 | 13165 | 0.0754 | 529 | 431 |
3×300 | 84.5 | 15700 | 0.0601 | 599 | 482 |
N2XSEYFGbY 3.6/6kV
Nom.Cross-apakan Area | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | mm | km/kg | Ω/km | A | A |
3×35 | 54.5 | 4860 | 0.524 | 172 | 154 |
3×50 | 58.0 | 5650 | 0.387 | 205 | 181 |
3×70 | 62.5 | 6670 | 0.268 | 253 | 220 |
3×95 | 66.0 | 7795 | 0.193 | 307 | 263 |
3×120 | 69.5 | 8765 | 0.153 | 352 | 298 |
3×150 | 73.0 | 10330 | 0.124 | 397 | 332 |
3×185 | 76.5 | 11775 | 0.0991 | 453 | 374 |
3×240 | 81.5 | 13855 | 0.0754 | 529 | 431 |
3×300 | 88.0 | 16295 | 0.0601 | 599 | 482 |
N2XSEYFGbY 6/10kV
Nom.Cross-apakan Area | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | mm | km/kg | Ω/km | A | A |
3×35 | 60.5 | 5570 | 0.524 | 172 | 154 |
3×50 | 63.5 | 6.365 | 0.387 | 205 | 181 |
3×70 | 67.5 | 7395 | 0.268 | 253 | 220 |
3×95 | 71.5 | 8555 | 0.193 | 307 | 263 |
3×120 | 75.0 | 9600 | 0.153 | 352 | 298 |
3×150 | 78.5 | 11195 | 0.124 | 397 | 332 |
3×185 | 82.0 | 12680 | 0.0991 | 453 | 374 |
3×240 | 87.0 | 14815 | 0.0754 | 529 | 431 |
3×300 | 93.5 | 17320 | 0.0601 | 599 | 482 |
N2XSEYFGbY 8.7/15kV
Nom.Cross-apakan Area | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | mm | km/kg | Ω/km | A | A |
3×35 | 65.5 | 6215 | 0.524 | 172 | 154 |
3×50 | 68.5 | 7070 | 0.387 | 205 | 181 |
3×70 | 73 | 8145 | 0.268 | 253 | 220 |
3×95 | 76.5 | 9310 | 0.193 | 307 | 263 |
3×120 | 80 | 10385 | 0.153 | 352 | 298 |
3×150 | 83.5 | 12050 | 0.124 | 397 | 332 |
3×185 | 87 | 13525 | 0.0991 | 453 | 374 |
3×240 | 92 | 15700 | 0.0754 | 529 | 431 |
3×300 | 98.5 | 18220 | 0.0601 | 599 | 482 |
N2XSEYFGbY 12/20kV
Cable Be
● Conductor:Compact stranded copper conductor,CI.2 as per IEC 60228
● Iboju oludari: Ologbele-adaorin
● Insulation:XLPE rated at 90°C
● Conducting Water Blocking Layer:Semi-conductive WBT
● ID Tape:Red/Yellow/Black
● Metallic Screen:Copper Tape Screen
● Metallic Screen:Copper Tape Screen
● Separator/Water Blocking Layer:Non-Conductive WBT
● Separation Sheath(for armoured cable):PVC inner Sheath(Fully extruded)
● Armoring:Galvanized Steel Flat Armor
Galvanized Steel Tape
●Sheath:PVC or FR-PVC type ST2/ST8 to IEC 60502,black
Ipilẹ koodu
YJ: XLPE idabobo
V: PVC apofẹlẹfẹlẹ
22: Double galvanized, irin waya armoring-3 ohun kohun
62: Irin alagbara, irin teepu armoring-1 mojuto
ZR: sooro ina
European Union:N2XSEYFGbY
Ohun elo
They are suitable for installation mostly in power supply stations, indoors and in cable ducts,outdoors,underground and in water as well as for installation on cable trays for industries,switchboards and power stations.
Standard
International:IEC 60502,EC60228,(IEC60332-3forZR-YJV22,ZR-YJV62only)
China:GB/T12706,(GB/T18380-3forZR-YJV22,ZR-YJV62only)
European standard:DIN VDE0276-620,HD620S2,IEC/EN 60228,IEC/EN 60502-2
Flame Retardant according to IEC/EN 60332-1-2
Indonesian Standard:Conductor:SNI IEC 60228/Insulation:SNI IEC 60502-2
Awọn iṣedede miiran bii BS, DIN ati ICEA lori ibeere
Imọ Data
Rated voltage:3.6/6KV 6/10KV 8.7/15KV 12/20KV
O pọju Adarí otutu: labẹ deede (90 ℃), pajawiri (130 ℃) tabi kukuru Circuit ko siwaju sii ju 5s (250 ℃) awọn ipo.
Min.Ambient Temp.-20°℃,Installation Temp.0℃
Min.Bending Radius:15× USB OD fun nikan mojuto
12× USB OD fun ọpọ mojuto
Awọn iwe-ẹri
CE, RoHS, CCC, KEMA ati diẹ sii ni ibeere