Paramètre
Surface nominale de la section transversale | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | mm | km/kg | Ω/km | A | A |
3×35 | 50.0 | 4355 | 0.524 | 172 | 154 |
3×50 | 53.0 | 5095 | 0.387 | 205 | 181 |
3×70 | 57.5 | 6045 | 0.268 | 253 | 220 |
3×95 | 61.5 | 7165 | 0.193 | 307 | 263 |
3×120 | 65.0 | 8105 | 0.153 | 352 | 298 |
3×150 | 68.0 | 9645 | 0.124 | 397 | 332 |
3×185 | 72.0 | 11055 | 0.0991 | 453 | 374 |
3×240 | 77.0 | 13165 | 0.0754 | 529 | 431 |
3×300 | 84.5 | 15700 | 0.0601 | 599 | 482 |
N2XSEYFGbY 3.6/6kV
Surface nominale de la section transversale | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | mm | km/kg | Ω/km | A | A |
3×35 | 54.5 | 4860 | 0.524 | 172 | 154 |
3×50 | 58.0 | 5650 | 0.387 | 205 | 181 |
3×70 | 62.5 | 6670 | 0.268 | 253 | 220 |
3×95 | 66.0 | 7795 | 0.193 | 307 | 263 |
3×120 | 69.5 | 8765 | 0.153 | 352 | 298 |
3×150 | 73.0 | 10330 | 0.124 | 397 | 332 |
3×185 | 76.5 | 11775 | 0.0991 | 453 | 374 |
3×240 | 81.5 | 13855 | 0.0754 | 529 | 431 |
3×300 | 88.0 | 16295 | 0.0601 | 599 | 482 |
N2XSEYFGbY 6/10kV
Surface nominale de la section transversale | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | mm | km/kg | Ω/km | A | A |
3×35 | 60.5 | 5570 | 0.524 | 172 | 154 |
3×50 | 63.5 | 6.365 | 0.387 | 205 | 181 |
3×70 | 67.5 | 7395 | 0.268 | 253 | 220 |
3×95 | 71.5 | 8555 | 0.193 | 307 | 263 |
3×120 | 75.0 | 9600 | 0.153 | 352 | 298 |
3×150 | 78.5 | 11195 | 0.124 | 397 | 332 |
3×185 | 82.0 | 12680 | 0.0991 | 453 | 374 |
3×240 | 87.0 | 14815 | 0.0754 | 529 | 431 |
3×300 | 93.5 | 17320 | 0.0601 | 599 | 482 |
N2XSEYFGbY 8.7/15kV
Surface nominale de la section transversale | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | mm | km/kg | Ω/km | A | A |
3×35 | 65.5 | 6215 | 0.524 | 172 | 154 |
3×50 | 68.5 | 7070 | 0.387 | 205 | 181 |
3×70 | 73 | 8145 | 0.268 | 253 | 220 |
3×95 | 76.5 | 9310 | 0.193 | 307 | 263 |
3×120 | 80 | 10385 | 0.153 | 352 | 298 |
3×150 | 83.5 | 12050 | 0.124 | 397 | 332 |
3×185 | 87 | 13525 | 0.0991 | 453 | 374 |
3×240 | 92 | 15700 | 0.0754 | 529 | 431 |
3×300 | 98.5 | 18220 | 0.0601 | 599 | 482 |
N2XSEYFGbY 12/20kV
Structure du câble
● Conductor:Compact stranded copper conductor,CI.2 as per IEC 60228
● Écran conducteur : semi-conducteur
● Insulation:XLPE rated at 90°C
● Conducting Water Blocking Layer:Semi-conductive WBT
● ID Tape:Red/Yellow/Black
● Metallic Screen:Copper Tape Screen
● Metallic Screen:Copper Tape Screen
● Separator/Water Blocking Layer:Non-Conductive WBT
● Separation Sheath(for armoured cable):PVC inner Sheath(Fully extruded)
● Armoring:Galvanized Steel Flat Armor
Galvanized Steel Tape
●Sheath:PVC or FR-PVC type ST2/ST8 to IEC 60502,black
Désignation du code
YJ : isolation XLPE
V:Gaine PVC
22 : Double blindage en fil d'acier galvanisé-3 noyaux
62 : Double blindage en ruban d'acier inoxydable-1 noyau
ZR : résistant aux flammes
European Union:N2XSEYFGbY
Application
They are suitable for installation mostly in power supply stations, indoors and in cable ducts,outdoors,underground and in water as well as for installation on cable trays for industries,switchboards and power stations.
Standard
International:IEC 60502,EC60228,(IEC60332-3forZR-YJV22,ZR-YJV62only)
China:GB/T12706,(GB/T18380-3forZR-YJV22,ZR-YJV62only)
European standard:DIN VDE0276-620,HD620S2,IEC/EN 60228,IEC/EN 60502-2
Flame Retardant according to IEC/EN 60332-1-2
Indonesian Standard:Conductor:SNI IEC 60228/Insulation:SNI IEC 60502-2
Autres normes telles que BS, DIN et ICEA sur demande
données techniques
Rated voltage:3.6/6KV 6/10KV 8.7/15KV 12/20KV
Température maximale du conducteur : dans des conditions normales (90 ℃), d'urgence (130 ℃) ou de court-circuit pas plus de 5 s (250 ℃).
Min.Ambient Temp.-20°℃,Installation Temp.0℃
Rayon de courbure minimum : 15 × diamètre extérieur du câble pour un seul noyau
12 × câble OD pour multicœur
Certificats
CE, RoHS, CCC, KEMA et plus d'autres sur demande