Nom. Cross-section Area | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | mm | km/kg | Ω/کیلومتره | A | A |
۳×۳۵ | 50.0 | 4355 | 0.524 | 172 | 154 |
3×50 | 53.0 | 5095 | 0.387 | 205 | 181 |
3×70 | 57.5 | 6045 | 0.268 | 253 | 220 |
۳×۹۵ | 61.5 | 7165 | 0.193 | 307 | 263 |
3×120 | 65.0 | 8105 | 0.153 | 352 | 298 |
3×150 | 68.0 | 9645 | 0.124 | 397 | 332 |
۳×۱۸۵ | 72.0 | 11055 | 0.0991 | 453 | 374 |
3×240 | 77.0 | 13165 | 0.0754 | 529 | 431 |
3×300 | 84.5 | 15700 | 0.0601 | 599 | 482 |
N2XSEYFGbY 3.6/6kV
Nom. Cross-section Area | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | mm | km/kg | Ω/کیلومتره | A | A |
۳×۳۵ | 54.5 | 4860 | 0.524 | 172 | 154 |
3×50 | 58.0 | 5650 | 0.387 | 205 | 181 |
3×70 | 62.5 | 6670 | 0.268 | 253 | 220 |
۳×۹۵ | 66.0 | 7795 | 0.193 | 307 | 263 |
3×120 | 69.5 | 8765 | 0.153 | 352 | 298 |
3×150 | 73.0 | 10330 | 0.124 | 397 | 332 |
۳×۱۸۵ | 76.5 | 11775 | 0.0991 | 453 | 374 |
3×240 | 81.5 | 13855 | 0.0754 | 529 | 431 |
3×300 | 88.0 | 16295 | 0.0601 | 599 | 482 |
N2XSEYFGbY 6/10kV
Nom. Cross-section Area | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | mm | km/kg | Ω/کیلومتره | A | A |
۳×۳۵ | 60.5 | 5570 | 0.524 | 172 | 154 |
3×50 | 63.5 | 6.365 | 0.387 | 205 | 181 |
3×70 | 67.5 | 7395 | 0.268 | 253 | 220 |
۳×۹۵ | 71.5 | 8555 | 0.193 | 307 | 263 |
3×120 | 75.0 | 9600 | 0.153 | 352 | 298 |
3×150 | 78.5 | 11195 | 0.124 | 397 | 332 |
۳×۱۸۵ | 82.0 | 12680 | 0.0991 | 453 | 374 |
3×240 | 87.0 | 14815 | 0.0754 | 529 | 431 |
3×300 | 93.5 | 17320 | 0.0601 | 599 | 482 |
N2XSEYFGbY 8.7/15kV
Nom. Cross-section Area | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | mm | km/kg | Ω/کیلومتره | A | A |
۳×۳۵ | 65.5 | 6215 | 0.524 | 172 | 154 |
3×50 | 68.5 | 7070 | 0.387 | 205 | 181 |
3×70 | 73 | 8145 | 0.268 | 253 | 220 |
۳×۹۵ | 76.5 | 9310 | 0.193 | 307 | 263 |
3×120 | 80 | 10385 | 0.153 | 352 | 298 |
3×150 | 83.5 | 12050 | 0.124 | 397 | 332 |
۳×۱۸۵ | 87 | 13525 | 0.0991 | 453 | 374 |
3×240 | 92 | 15700 | 0.0754 | 529 | 431 |
3×300 | 98.5 | 18220 | 0.0601 | 599 | 482 |
N2XSEYFGbY 12/20kV
د کیبل جوړښت
● Conductor:Compact stranded copper conductor,CI.2 as per IEC 60228
● کنډکټر سکرین: نیم کنډکټر
● Insulation:XLPE rated at 90°C
● Conducting Water Blocking Layer:Semi-conductive WBT
● ID Tape:Red/Yellow/Black
● Metallic Screen:Copper Tape Screen
● Metallic Screen:Copper Tape Screen
● Separator/Water Blocking Layer:Non-Conductive WBT
● Separation Sheath(for armoured cable):PVC inner Sheath(Fully extruded)
● Armoring:Galvanized Steel Flat Armor
Galvanized Steel Tape
●Sheath:PVC or FR-PVC type ST2/ST8 to IEC 60502,black
د کوډ نومول
YJ: XLPE موصلیت
V: PVC میان
22: ډبل ګالنيز فولادو تار زغره وال - 3 کور
62: ډبل سټینلیس سټیل ټیپ زغره وال - 1 کور
ZR: د اور مقاومت
European Union:N2XSEYFGbY
غوښتنلیک
They are suitable for installation mostly in power supply stations, indoors and in cable ducts,outdoors,underground and in water as well as for installation on cable trays for industries,switchboards and power stations.
معیاري
International:IEC 60502,EC60228,(IEC60332-3forZR-YJV22,ZR-YJV62only)
China:GB/T12706,(GB/T18380-3forZR-YJV22,ZR-YJV62only)
European standard:DIN VDE0276-620,HD620S2,IEC/EN 60228,IEC/EN 60502-2
Flame Retardant according to IEC/EN 60332-1-2
Indonesian Standard:Conductor:SNI IEC 60228/Insulation:SNI IEC 60502-2
نور معیارونه لکه BS، DIN او ICEA په غوښتنه
تخنیکي ډاټا
Rated voltage:3.6/6KV 6/10KV 8.7/15KV 12/20KV
اعظمي کنډکټر تودوخه: د نورمال لاندې (90 ℃) ، اضطراري (130 ℃) یا شارټ سرکټ له 5s (250 ℃) شرایطو څخه ډیر نه وي.
Min.Ambient Temp.-20°℃,Installation Temp.0℃
Min.Bending Radius:15×Cable OD د واحد کور لپاره
د ملټي کور لپاره 12 × کیبل OD
سندونه
CE، RoHS، CCC، KEMA او نور په غوښتنه کې