Parameter
Nom.Cross-section Area |
overall diameter |
cable Weight |
DC Resistance at 20℃ Conductor min |
Current Carrying Capacity at 30℃ |
|
In Air | In Ground | ||||
mm² | mm | km/kg | Ω/km | A | |
3×25 | 43 | 3660 | 0.727 | 133 | 132 |
3×35 | 45 | 4175 | 0.524 | 172 | 170 |
3×50 | 49 | 5260 | 0.387 | 205 | 201 |
3×70 | 53 | 6330 | 0.268 | 256 | 245 |
3×95 | 57 | 7555 | 0.193 | 312 | 294 |
3×120 | 60 | 8640 | 0.153 | 359 | 334 |
3×150 | 63 | 9840 | 0.124 | 409 | 375 |
3×185 | 68 | 11510 | 0.0991 | 468 | 424 |
3×240 | 76 | 14490 | 0.0754 | 552 | 492 |
3×300 | 82 | 17587 | 0.0601 | 627 | 552 |
N2XSERGbY 3.6/6kV
Nom.Cross-section Area |
overall diameter |
cable Weight |
DC Resistance at 20℃ Conductor min |
Current Carrying Capacity at 30℃ |
|
In Air | In Ground | ||||
mm² | mm | km/kg | Ω/km | A | |
3×25 | 48 | 4600 | 0.727 | 134 | 133 |
3×35 | 51 | 5220 | 0.524 | 173 | 171 |
3×50 | 54 | 5925 | 0.387 | 206 | 202 |
3×70 | 57 | 6985 | 0.268 | 257 | 246 |
3×95 | 62 | 8310 | 0.193 | 313 | 295 |
3×120 | 65 | 9415 | 0.153 | 360 | 335 |
3×150 | 68 | 10572 | 0.124 | 410 | 376 |
3×185 | 75 | 13015 | 0.0991 | 469 | 425 |
3×240 | 78 | 15424 | 0.0754 | 553 | 493 |
3×300 | 85 | 18210 | 0.0601 | 628 | 553 |
N2XSERGbY 6/10kV
Nom.Cross-section Area |
overall diameter |
cable Weight |
DC Resistance at 20℃ Conductor min |
Current Carrying Capacity at 30℃ |
|
In Air | In Ground | ||||
mm² | mm | km/kg | Ω/km | A | |
3×25 | 54 | 5432 | 0.727 | 134 | 132 |
3×35 | 56 | 5992 | 0.524 | 173 | 171 |
3×50 | 59 | 6723 | 0.387 | 206 | 202 |
3×70 | 63 | 7922 | 0.268 | 257 | 246 |
3×95 | 67 | 9210 | 0.193 | 313 | 295 |
3×120 | 70 | 10355 | 0.153 | 360 | 335 |
3×150 | 73 | 11530 | 0.124 | 410 | 376 |
3×185 | 79 | 14275 | 0.0991 | 469 | 425 |
3×240 | 84 | 16650 | 0.0754 | 553 | 492 |
3×300 | 90 | 19354 | 0.0601 | 629 | 554 |
N2XSERGbY 8.7/15kV
Nom.Cross-section Area |
overall diameter |
cable Weight |
DC Resistance at 20℃ Conductor min |
Current Carrying Capacity at 30℃ |
|
In Air | In Ground | ||||
mm² | mm | km/kg | Ω/km | A | |
3×35 | 61 | 6748 | 0.524 | 173 | 171 |
3×50 | 64 | 7588 | 0.387 | 206 | 202 |
3×70 | 68 | 8720 | 0.268 | 257 | 246 |
3×95 | 72 | 10075 | 0.193 | 313 | 295 |
3×120 | 76 | 12082 | 0.153 | 360 | 335 |
3×150 | 79 | 13325 | 0.124 | 410 | 376 |
3×185 | 84 | 15310 | 0.0991 | 469 | 425 |
3×240 | 89 | 17685 | 0.0754 | 553 | 492 |
3×300 | 95 | 20480 | 0.0601 | 629 | 554 |
N2XSEFGbY 12/20kV
Nom.Cross-section Area |
overall diameter |
cable Weight |
DC Resistance at 20℃ Conductor min |
Current Carrying Capacity at 30℃ |
|
In Air | In Ground | ||||
mm² | mm | km/kg | Ω/km | A | |
3×50 | 78 | 10,645 | 0.387 | 207 | 202 |
3×70 | 82 | 12,000 | 0.268 | 257 | 246 |
3×95 | 86 | 13,465 | 0.193 | 313 | 295 |
3×120 | 89 | 14.76 | 0.153 | 360 | 335 |
3×150 | 92 | 16,070 | 0.124 | 410 | 376 |
3×185 | 97 | 18,075 | 0.0991 | 469 | 425 |
3×240 | 101 | 20,550 | 0.0754 | 553 | 492 |
3×300 | 107 | 23,615 | 0.0601 | 629 | 554 |
N2XSEFGbY 18/30kV
Cable Structure
● Conductor:Compact stranded copper conductor,CI.2 as per IEC 60228
● Conductor Screen: Semi-conductor
● Insulation:XLPE rated at 90°C
● ID Tape:Red/Yellow/Black
● Metallic Screen:Copper Tape Screen
● Polyster Tape
● Separation Sheath(for armoured cable):PVC inner Sheath(Fully extruded)
● Armoring:Galvanized Steel Flat Armor
Galvanized Steel Tape
●Sheath:PVC or FR-PVC type ST2/ST8 to IEC 60502,black
Code Designation
YJ:XLPE insulation
V:PVC sheath
22:Double galvanized steel wire armoring-3 cores
62:Double stainless steel tape armoring-1 core
ZR:Flame resistant
European Union:N2XSERGBY/NA2XSERGBY
Application
For installation in the ground, indoors,cable trunking and outdoors if increased mechanical protection is required or where high-pulling stresses may occur during installation or operation.
Standard
International:IEC 60502,EC60228,(IEC60332-3forZR-YJV22,ZR-YJV62only)
China:GB/T12706,(GB/T18380-3forZR-YJV22,ZR-YJV62only)
European standard:DIN VDE0276-620,HD620S2,IEC/EN 60228,IEC/EN 60502-2
Flame Retardant according to IEC/EN 60332-1-2
Indonesian Standard:Conductor:SNI IEC 60228/Insulation:SNI IEC 60502-2
Other standards such as BS,DIN and ICEA upon request
Technical Data
Rated voltage:3.6/6KV6/10KV 8.7/15KV 12/20KV 18/30kV
Maximum Conductor Temperature:under normal (90℃),emergency(130℃)or short circuit no more than 5s (250℃)conditions.
Min.Ambient Temp.-20°℃,Installation Temp.0℃
Min.Bending Radius:15×cable O.D for single core
12×cable O.D for multi core
Certificates
CE,RoHS,CCC,KEMA and more others at request