ကန့်သတ်ချက်
Nom.Cross-section Area | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | မီလီမီတာ | km/kg | Ω/ကီလိုမီတာ | A | A |
၃×၂၅ | 38.5 | 2603 | 0.727 | 152 | 147 |
၃×၃၅ | 41.5 | 3074 | 0.524 | 185 | 175 |
၃×၅၀ | 44.5 | 3641 | 0.387 | 219 | 205 |
၃×၇၀ | 48.5 | 4536 | 0.268 | 273 | 251 |
၃×၉၅ | 52 | 5542 | 0.193 | 330 | 299 |
၃×၁၂၀ | 56 | 6516 | 0.153 | 379 | 339 |
၃×၁၅၀ | 59.5 | 7593 | 0.124 | 430 | 379 |
၃×၁၈၅ | 63 | 8940 | 0.0991 | 490 | 427 |
၃×၂၄၀ | 69 | 11074 | 0.0754 | 573 | 490 |
၃×၃၀၀ | 75.5 | 13395 | 0.0601 | 649 | 547 |
N2XSEFGbY 3.6/6kV
Nom.Cross-section Area | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | မီလီမီတာ | km/kg | Ω/ကီလိုမီတာ | A | A |
၃×၂၅ | 43 | 2984 | 0.727 | 155 | 147 |
၃×၃၅ | 46 | 3515 | 0.524 | 187 | 175 |
၃×၅၀ | 48.5 | 4061 | 0.387 | 222 | 205 |
၃×၇၀ | 52.5 | 4955 | 0.268 | 276 | 251 |
၃×၉၅ | 56.5 | 6055 | 0.193 | 333 | 298 |
၃×၁၂၀ | 60 | 7026 | 0.153 | 382 | 339 |
၃×၁၅၀ | 63.5 | 8110 | 0.124 | 433 | 379 |
၃×၁၈၅ | 67.5 | 9478 | 0.0991 | 493 | 426 |
၃×၂၄၀ | 73.5 | 11663 | 0.0754 | 574 | 489 |
၃×၃၀၀ | 78.5 | 13814 | 0.0601 | 650 | 546 |
N2XSEFGbY 6/10kV
Nom.Cross-section Area | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | မီလီမီတာ | km/kg | Ω/ကီလိုမီတာ | A | A |
၃×၂၅ | 49 | 3552 | 0.727 | 156 | 146 |
၃×၃၅ | 51.5 | 4072 | 0.524 | 189 | 174 |
၃×၅၀ | 54 | 4606 | 0.387 | 225 | 205 |
၃×၇၀ | 58.5 | 5619 | 0.268 | 278 | 250 |
၃×၉၅ | 62 | 6697 | 0.193 | 336 | 298 |
၃×၁၂၀ | 65.5 | 7705 | 0.153 | 385 | 338 |
၃×၁၅၀ | 69 | 8810 | 0.124 | 435 | 378 |
၃×၁၈၅ | 73 | 10284 | 0.0991 | 494 | 424 |
၃×၂၄၀ | 79 | 12429 | 0.0754 | 577 | 488 |
၃×၃၀၀ | 83.5 | 14586 | 0.0601 | 654 | 547 |
N2XSEFGbY 8.7/15kV
Nom.Cross-section Area | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | မီလီမီတာ | km/kg | Ω/ကီလိုမီတာ | A | A |
၃×၃၅ | 56.5 | 4624 | 0.524 | 190 | 174 |
၃×၅၀ | 59 | 5185 | 0.387 | 226 | 205 |
၃×၇၀ | 63 | 6194 | 0.268 | 280 | 250 |
၃×၉၅ | 66.5 | 7276 | 0.193 | 338 | 298 |
၃×၁၂၀ | 70 | 8318 | 0.153 | 387 | 338 |
၃×၁၅၀ | 74 | 9516 | 0.124 | 437 | 377 |
၃×၁၈၅ | 78 | 10981 | 0.0991 | 496 | 424 |
၃×၂၄၀ | 83.5 | 13130 | 0.0754 | 579 | 488 |
၃×၃၀၀ | 88.5 | 15374 | 0.0601 | 655 | 546 |
N2XSEFGbY 12/20kV
Nom.Cross-section Area | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min | Current Carrying Capacity at 30℃ | |
In Air | In Ground | ||||
mm² | မီလီမီတာ | km/kg | Ω/ကီလိုမီတာ | A | A |
၃×၅၀ | 71 | 6738 | 0.387 | 229 | 204 |
၃×၇၀ | 75.5 | 7869 | 0.268 | 282 | 249 |
၃×၉၅ | 79 | 9021 | 0.193 | 340 | 296 |
၃×၁၂၀ | 82.5 | 10109 | 0.153 | 389 | 336 |
၃×၁၅၀ | 86 | 11335 | 0.124 | 440 | 376 |
၃×၁၈၅ | 90 | 12808 | 0.0991 | 500 | 423 |
၃×၂၄၀ | 95.5 | 15124 | 0.0754 | 582 | 487 |
၃×၃၀၀ | 101 | 17512 | 0.0601 | 657 | 545 |
N2XSEFGbY 18/30kV
Cable Structure ၊
● Conductor:Compact stranded copper conductor,CI.2 as per IEC 60228
● စပယ်ယာ မျက်နှာပြင်- တစ်ပိုင်းလျှပ်ကူးပစ္စည်း
● Insulation:XLPE rated at 90°C
● ID Tape:Red/Yellow/Black
● Metallic Screen:Copper Tape Screen
● ID Tape:Red/Yellow/Black
● Separation Sheath(for armoured cable):PVC inner Sheath(Fully extruded)
● Armoring:Galvanized Steel Flat Armor
Galvanized Steel Tape
●Sheath:PVC or FR-PVC type ST2/ST8 to IEC 60502,black
ကုဒ်သတ်မှတ်ခြင်း။
YJ:XLPE အကာအကွယ်
V: PVC အစွပ်
22: နှစ်ထပ်သွပ်ရည်စိမ်သံမဏိဝါယာချပ်ကာ-3 cores
62: နှစ်ထပ်သံမဏိတိပ်ချပ်ဝတ်တန်ဆာ-1 အူတိုင်
ZR: မီးဒဏ်ခံနိုင်ရည်ရှိသည်။
European Union:N2XSEFGbY/NA2XSEFGbY
လျှောက်လွှာ
For installation in the ground, indoors,cable trunking and outdoors if increased mechanical protection is required or where high-pulling stresses may occur during installation or operation.
စံ
International:IEC 60502,EC60228,(IEC60332-3forZR-YJV22,ZR-YJV62only)
China:GB/T12706,(GB/T18380-3forZR-YJV22,ZR-YJV62only)
European standard:DIN VDE0276-620,HD620S2,IEC/EN 60228,IEC/EN 60502-2
Flame Retardant according to IEC/EN 60332-1-2
Indonesian Standard:Conductor:SNI IEC 60228/Insulation:SNI IEC 60502-2
တောင်းဆိုချက်အရ BS၊ DIN နှင့် ICEA ကဲ့သို့သော အခြားစံနှုန်းများ
နည်းပညာဆိုင်ရာဒေတာ
Rated voltage:3.6/6KV6/10KV 8.7/15KV 12/20KV 18/30kV
အများဆုံး လျှပ်ကူးတာ အပူချိန်- ပုံမှန် (90 ℃)၊ အရေးပေါ် (130 ℃) သို့မဟုတ် 5 စက္ကန့် (250 ℃) ထက် မပိုသော ပတ်လမ်းတို။
Min.Ambient Temp.-20°℃,Installation Temp.0℃
ပင်မတစ်ခုတည်းအတွက် အနိမ့်ပိုင်းကွေးအချင်း- 15 × ကေဘယ် OD
multi core အတွက် 12× cable OD
အောင်လက်မှတ်များ
တောင်းဆိုချက်အရ CE၊ RoHS၊ CCC၊ KEMA နှင့် အခြားအရာများ