N2XSEFGbY/NA2XSEFGbY 3.6/6kV 6/10kV 8.7/15kV 12/20kV 18/30kV MEDIUM VOLTAGE Cu(AL) CONDUCTOR XLPE INSULATED MULTI-CORE STEEL TAPE ARMOURED POWER CABLE

Model Number:N2XSEFGbY/NA2XSEFGbYCu(AI)/XLPE/CTS/PVC/SFWA/PVC,  3.6/6kV 6/10kV 8.7/15kV 12/20kV 18/30kV
Category: Energy Cables / Power Cables / Industrial Cable
Plak fan oarsprong: XingTai, Sina
Merknamme: TIANHUAN
Certification ISO,CE,IEC,TUV

Minimum order quantity:5000 meters





DOWNLOAD PDF
Details
Tags

Parameter

Nom.Cross-section Area overall diameter cable Weight DC Resistance at 20℃ Conductor min Current Carrying Capacity at 30℃
In Air In Ground
mm² mm km/kg Ω/km A A
3×25 38.5 2603 0.727 152 147
3×35 41.5 3074 0.524 185 175
3x50 44.5 3641 0.387 219 205
3x70 48.5 4536 0.268 273 251
3x95 52 5542 0.193 330 299
3×120 56 6516 0.153 379 339
3×150 59.5 7593 0.124 430 379
3×185 63 8940 0.0991 490 427
3×240 69 11074 0.0754 573 490
3×300 75.5 13395 0.0601 649 547

                                 N2XSEFGbY 3.6/6kV

 

Nom.Cross-section Area overall diameter cable Weight DC Resistance at 20℃ Conductor min Current Carrying Capacity at 30℃
In Air In Ground
mm² mm km/kg Ω/km A A
3×25 43 2984 0.727 155 147
3×35 46 3515 0.524 187 175
3x50 48.5 4061 0.387 222 205
3x70 52.5 4955 0.268 276 251
3x95 56.5 6055 0.193 333 298
3×120 60 7026 0.153 382 339
3×150 63.5 8110 0.124 433 379
3×185 67.5 9478 0.0991 493 426
3×240 73.5 11663 0.0754 574 489
3×300 78.5 13814 0.0601 650 546

                                    N2XSEFGbY 6/10kV

 

Nom.Cross-section Area overall diameter cable Weight DC Resistance at 20℃ Conductor min Current Carrying Capacity at 30℃
In Air In Ground
mm² mm km/kg Ω/km A A
3×25 49 3552 0.727 156 146
3×35 51.5 4072 0.524 189 174
3x50 54 4606 0.387 225 205
3x70 58.5 5619 0.268 278 250
3x95 62 6697 0.193 336 298
3×120 65.5 7705 0.153 385 338
3×150 69 8810 0.124 435 378
3×185 73 10284 0.0991 494 424
3×240 79 12429 0.0754 577 488
3×300 83.5 14586 0.0601 654 547

                                        N2XSEFGbY 8.7/15kV

 

Nom.Cross-section Area overall diameter cable Weight DC Resistance at 20℃ Conductor min Current Carrying Capacity at 30℃
In Air In Ground
mm² mm km/kg Ω/km A A
3×35 56.5 4624 0.524 190 174
3x50 59 5185 0.387 226 205
3x70 63 6194 0.268 280 250
3x95 66.5 7276 0.193 338 298
3×120 70 8318 0.153 387 338
3×150 74 9516 0.124 437 377
3×185 78 10981 0.0991 496 424
3×240 83.5 13130 0.0754 579 488
3×300 88.5 15374 0.0601 655 546

                                     N2XSEFGbY 12/20kV                                       

 

Nom.Cross-section Area overall diameter cable Weight DC Resistance at 20℃ Conductor min Current Carrying Capacity at 30℃
In Air In Ground
mm² mm km/kg Ω/km A A
3x50 71 6738 0.387 229 204
3x70 75.5 7869 0.268 282 249
3x95 79 9021 0.193 340 296
3×120 82.5 10109 0.153 389 336
3×150 86 11335 0.124 440 376
3×185 90 12808 0.0991 500 423
3×240 95.5 15124 0.0754 582 487
3×300 101 17512 0.0601 657 545

                                  N2XSEFGbY 18/30kV                                  

Kabel Struktuer

● Conductor:Compact stranded copper conductor,CI.2 as per IEC 60228

● Dirigint Skerm: Semi-conductor

● Insulation:XLPE rated at 90°C

● ID Tape:Red/Yellow/Black

● Metallic Screen:Copper Tape Screen

● ID Tape:Red/Yellow/Black

● Separation Sheath(for armoured cable):PVC inner Sheath(Fully extruded)

● Armoring:Galvanized Steel Flat Armor

              Galvanized Steel Tape

●Sheath:PVC or FR-PVC type ST2/ST8 to IEC 60502,black

Koade oantsjutting

YJ: XLPE isolaasje

V: PVC mantel

22: Dûbele galvanisearre stielen wire armoring-3 kearnen

62: Dûbele roestfrij stiel tape armoring-1 kearn

ZR: flammebestindich

European Union:N2XSEFGbY/NA2XSEFGbY

Oanfraach

For installation in the ground, indoors,cable trunking and outdoors if increased mechanical protection is required or where high-pulling stresses may occur during installation or operation.

Standert

International:IEC 60502,EC60228,(IEC60332-3forZR-YJV22,ZR-YJV62only)

China:GB/T12706,(GB/T18380-3forZR-YJV22,ZR-YJV62only)

European standard:DIN VDE0276-620,HD620S2,IEC/EN 60228,IEC/EN 60502-2

                            Flame Retardant according to IEC/EN 60332-1-2

Indonesian Standard:Conductor:SNI IEC 60228/Insulation:SNI IEC 60502-2

Oare noarmen lykas BS, DIN en ICEA op oanfraach

Technyske data

Rated voltage:3.6/6KV6/10KV 8.7/15KV 12/20KV 18/30kV

Maksimale konduktemperatuer: ûnder normale (90 ℃), need (130 ℃) of koartsluting net mear dan 5 s (250 ℃) betingsten.

Min.Ambient Temp.-20°℃,Installation Temp.0℃

Min.Bending Radius: 15 × kabel OD foar inkele kearn 

                             12 × kabel OD foar multi core