Parameter
Nom.Cross-section Area | overall diameter | cable Weight | DC Resistance at 20℃ Conductor min |
mm² | mm | km/kg | Ω/km |
3×0.75 | 8.7 | 91 | 26 |
3×1 | 9 | 98 | 19.5 |
3×1.5 | 10.1 | 122 | 13.3 |
3×2.5 | 11.3 | 176 | 7.98 |
3×4 | 22 | 225 | 4.95 |
4×0.75 | 9.2 | 120 | 26 |
4×1 | 9.6 | 110 | 19.5 |
4×1.5 | 10.8 | 150 | 13.3 |
4×2.5 | 12.2 | 209 | 7.98 |
4×4 | 14 | 311 | 4.95 |
4×6 | 15.7 | 429 | 3.3 |
4×10 | 19.5 | 759 | 1.91 |
4×16 | 21.9 | 1093 | 1.21 |
4×25 | 30 | 1593 | 0.78 |
4×35 | 33 | 2390 | 0.554 |
4×50 | 40 | 3400 | 0.386 |
4×70 | 46 | 4750 | 0.272 |
5×0.75 | 9.9 | 134 | 26 |
5×1 | 10.4 | 136 | 19.5 |
5×1.5 | 11.7 | 176 | 13.3 |
5×2.5 | 13.3 | 252 | 7.98 |
5×4 | 15.3 | 398 | 4.95 |
5×6 | 17.9 | 602 | 3.3 |
5×10 | 23 | 927 | 1.91 |
5×16 | 27 | 1583 | 1.21 |
5×25 | 33.8 | 2040 | 0.78 |
5×35 | 36.9 | 2887 | 0.554 |
7×0.75 | 11.1 | 177 | 26 |
7×1 | 12.1 | 179 | 19.5 |
7×1.5 | 13.5 | 192 | 13.3 |
7×2.5 | 15.2 | 335 | 7.98 |
7×4 | 16.8 | 524 | 4.95 |
7×6 | 19.7 | 802 | 3.3 |
12×0.75 | 13.4 | 248 | 26 |
12×1 | 14.5 | 287 | 19.5 |
12×1.5 | 16.6 | 363 | 13.3 |
12×2.5 | 18.7 | 544 | 7.98 |
18×0.75 | 15.6 | 350 | 26 |
18×1 | 17.3 | 408 | 19.5 |
18×1.5 | 19.7 | 520 | 13.3 |
18×2.5 | 22 | 788 | 7.98 |
25×0.75 | 18.9 | 478 | 26 |
25×1 | 21.1 | 567 | 19.5 |
25×1.5 | 23.9 | 740 | 13.3 |
34×0.75 | 21.5 | 626 | 26 |
34×1 | 24 | 751 | 19.5 |
34×1.5 | 27.2 | 959 | 13.3 |
42×0.75 | 23.3 | 760 | 26 |
42×1 | 25.9 | 890 | 19.5 |
42×1.5 | 29.5 | 1110 | 13.3 |
50×0.75 | 25.6 | 871 | 26 |
50×1 | 28.5 | 1076 | 19.5 |
50×1.5 | 32.5 | 1399 | 13.3 |
61×0.75 | 28.2 | 1060 | 26 |
61×1.5 | 36.8 | 1680 | 19.5 |
Cable Structure
● Conductor:Class 5 flexible stranded bare copper
● Insulation:PVC
● Sheath:Special PVC-Compound
Code Designation
YSLY
Application
Flexible power,process control and instrumentation cable for industry,machinery and outdoor environment.The YSLY cable is resistant against most usual chemicals,oil and grease
Standard
European standard :IEC/EN 60811-404
Fire Retardant according to:IEC/EN 60332-1-2
Other standards such as IEC,BS,DIN and ICEA upon request
Technical Data
Voltage Rating Uo/U:0.6/1kV
Temperature Rating:Fixed:-20℃ to+70℃
Installation:-5℃ to+70℃
Minimum Bending Radius :Fixed:4×overall diameter
Flexed:7.5×overall diameter
Certificates
CE,RoHS,CCC,KEMA and more others at request