Parameter
Nom.Cross-section Area | Nominal Thickness Insulation | overall diameter | cable Weight | DC Resistance at 20℃Insulation min | Current Carrying Capacity at 30℃ | |
In Air | In Pipe | |||||
mm² | mm | mm | km/kg | M.Ω.km | mm² | mm |
1 × 1.5 re | 0.7 | 3.0 | 18 | 1121 | 27 | 17 |
1 × 1.5 rm | 0.7 | 3.0 | 19 | 1020 | 27 | 17 |
1 × 2.5 re | 0.7 | 3.2 | 28 | 940 | 37 | 23 |
1 × 2.5 rm | 0.7 | 3.5 | 29 | 842 | 37 | 23 |
1 × 4 re | 0.7 | 3.7 | 42 | 784 | 49 | 29 |
1 × 4 rm | 0.7 | 4.0 | 44 | 704 | 49 | 29 |
1 × 6 re | 0.7 | 4.2 | 61 | 667 | 62 | 36 |
1 × 6 rm | 0.7 | 4.6 | 63 | 590 | 62 | 36 |
1 × 10 re | 0.7 | 5.0 | 99 | 538 | 85 | 52 |
1 × 10 rm | 0.7 | 5.5 | 103 | 473 | 85 | 52 |
1 × 16 rm | 0.7 | 6.6 | 159 | 392 | 112 | 70 |
1 × 25 rm | 0.9 | 8.3 | 253 | 400 | 161 | 95 |
1 × 35 rm | 0.9 | 9.5 | 346 | 348 | 182 | 119 |
1 × 50 rm | 1.0 | 11 | 462 | 326 | 226 | 151 |
1 × 70 rm | 1.1 | 13 | 664 | 303 | 283 | 190 |
1 × 95 rm | 1.1 | 15 | 912 | 262 | 336 | 227 |
1 × 120 rm | 1.2 | 17 | 1147 | 254 | 396 | 271 |
1 × 150 rm | 1.4 | 19 | 1413 | 266 | 449 | —— |
1 × 185 rm | 1.6 | 21 | 1775 | 271 | 514 | —— |
1 × 240 rm | 1.7 | 24 | 2332 | 252 | 607 | —— |
1 × 300 rm | 1.8 | 27 | 2904 | 240 | 669 | —— |
1 × 400 rm | 2.0 | 30 | 3710 | 235 | 831 | —— |
1 × 500 rm | 2.2 | 34 | 4673 | 228 | 950 | —— |
Cable Structure
● Conductor: [re] round solid conductor
[rm] circular stranded conductor
● Insulation: XLPE
Code Designation
N2XA
Application
For Installations as underground,outdoor ,indoor,in ducts and where mechanical protection is required or for higher tensile stresses during installation and operation.
Standard
Indonesia standards:Conductor SNI IEC 60228,SPLN 41-1,insulation SNI IEC 60502-1,SPLN 41-9
Technical Data
Rated voltage:U0/U 0.6/1 kV
Temperature Rating Maximum Operating: +90℃
Maximum Short-Circuit :+250℃
Minimum. Bending Radius:15×overall diameter