Paramèter
No.inti × salib sek. |
AVG. Isolasi kekandelan |
Jaket AVG (Sarung) kekandelan |
Kira-kira. OD | Kira-kira. Bobot | Resistansi konduktor ing 20 ° C |
mm² | mm | mm | mm | kg/km | Ω/km |
1×2.5 | 0.8 | 0.8 | 5 | 47 | 8.21 |
1×4 | 0.8 | 0.9 | 5.6 | 64 | 5.09 |
1×6 | 0.8 | 0.9 | 6.2 | 87 | 3.39 |
1×10 | 1 | 1 | 7.5 | 132 | 1.95 |
1×16 | 1 | 1 | 8.7 | 197 | 1.24 |
1×25 | 1.2 | 1.2 | 10.8 | 304 | 0.795 |
1×35 | 1.2 | 1.2 | 12.4 | 413 | 0.565 |
1×50 | 14.4 | 576 | 0.393 | ||
1×70 | 16.2 | 781 | 0.277 | ||
1×95 | 18.3 | 1036 | 0.210 | ||
1×120 | 19.9 | 1287 | 0.164 | ||
1×150 | 22.1 | 1607 | 0.132 | ||
1×185 | 24.8 | 1993 | 0.108 | ||
1×240 | 27.8 | 2555 | 0.0817 |
Struktur Kabel
Tembaga Bare, tinned, sacoro apik terdampar miturut
kanggo IEC 60228 cl.5
Insulated kaping pindho
Isolasi silang Polyolefin
Sarung njaba Polyolefin sing disambung silang
Werna klambi ireng, abang utawa biru
Properti
Ozon tahan acc.to EN 50396
•Weather lan tahan UV acc.to HD 605/A1
• Bebas Halogen acc.to EN 50267-2-1, EN 60684-2
•Tahan kanggo asam lan basa acc.toEN 60811-2-1 tahan geni acc.to VDE 0482-332-1-2,DIN EN 60332-1-2,IEC 60332-1
•Sarung sing kuat lan tahan abrasi acc.to DiN EN 53516
•Tahan kanggo short-circuit nganti 200'C thanks kanggo jampel pindho; short-circuit suhu 200'C/5 sec.
•Hidrolisis lan tahan amonia
Aplikasi
Kabel PV inti tunggal nyukupi kabutuhan sing beda-beda saka Industri Solar. Aplikasi kalebu sambungan menyang kothak persimpangan modul; nuntun kabel dibutuhake ing integrasi sistem imbangan Rated 1000V
Data Teknis
• Kisaran suhu -40 ℃ nganti + 90 ℃ Max.temp.at konduktor + 120C
•Tegangan nominal Miturut VDE U,/U 600/1000 V AC 1800 V DC konduktor/konduktor
Tegangan tes AC 10000 V
instalasi foued approx. 8 x diameteripun njaba flexóing 10 × diameteripun kabel
Standar
TÜV(2 PfG 1169/08.2007,R60025298) Complant RoHS