NYFGBY 0.6/1kv Cu conductors PVC insulated Galvanized Flar Steel Wire Armor and PVC sheathed power cable
Պարամետր
Nom.Խաչհատվածի տարածք | Nominal Thickness | overall diameter | cable Weight | DC Resistance at 20℃Insulation min | Current Carrying Capacity at 30℃ | ||
Մեկուսացում | Outer Sheath | In Air | In Ground | ||||
մմ² | մմ² | մմ | մմ | km/kg | M.Ω.km | A | A |
2 × 25 rm | 1.2 | 1.8 | 24.9 | 1383 | 5 | 134 | 120 |
2 × 35 rm | 1.2 | 1.8 | 27.1 | 1709 | 4 | 160 | 150 |
2 × 50 rm | 1.4 | 1.9 | 30.5 | 2170 | 4 | 187 | 180 |
2 × 70 rm | 1.4 | 2.0 | 34.5 | 2846 | 4 | 230 | 230 |
2 × 95 rm | 1.6 | 2.1 | 39.2 | 3702 | 4 | 280 | 275 |
2 ×120 rm | 1.6 | 2.2 | 42.5 | 4423 | 3 | 320 | 320 |
2 ×150 rm | 1.8 | 2.3 | 46.9 | 5347 | 3 | 355 | 379 |
2 × 185 rm | 2.0 | 2.5 | 51.8 | 6501 | 3 | 409 | 430 |
2 × 240 rm | 2.2 | 2.7 | 58 | 8231 | 3 | 472 | 510 |
2 × 300 rm | 2.4 | 2.8 | 64.1 | 10081 | 3 | 525 | 590 |
3 × 16 rm | 1.0 | 1.8 | 22.6 | 1010 | 5 | 89 | 80 |
3 × 25 rm | 1.2 | 1.8 | 26.2 | 1695 | 5 | 116 | 105 |
3 × 35 rm | 1.2 | 1.8 | 28.6 | 2084 | 4 | 138 | 130 |
3 × 50 rm | 1.4 | 1.9 | 28.1 | 2403 | 4 | 165 | 160 |
3 × 70 rm | 1.4 | 2.0 | 31.3 | 3112 | 4 | 205 | 200 |
3 × 95 rm | 1.6 | 2.2 | 35.6 | 4151 | 4 | 245 | 245 |
3 × 120 rm | 1.6 | 2.3 | 38.4 | 5041 | 3 | 285 | 285 |
3 × 150 rm | 1.8 | 2.4 | 42.2 | 6121 | 3 | 315 | 325 |
3 × 185 rm | 2.0 | 2.6 | 46.8 | 7377 | 3 | 355 | 370 |
3 × 240 rm | 2.2 | 2.8 | 52.3 | 9536 | 3 | 415 | 435 |
3 × 300 rm | 2.4 | 3.0 | 57.4 | 11717 | 3 | 465 | 500 |
4 × 10 re | 1.0 | 1.8 | 22.2 | 1073 | 7 | 69 | 80 |
4 × 10 rm | 1.0 | 1.8 | 23 | 1101 | 6 | 69 | 80 |
4 × 16 rm | 1.0 | 1.8 | 26 | 1455 | 5 | 89 | 80 |
4 × 25 rm | 1.2 | 1.8 | 30 | 2093 | 5 | 116 | 105 |
4 × 35 rm | 1.2 | 1.9 | 33 | 2602 | 4 | 138 | 130 |
4 × 50 sm | 1.4 | 2.0 | 35 | 3080 | 4 | 165 | 160 |
4 × 70 sm | 1.4 | 2.1 | 38 | 4093 | 4 | 205 | 200 |
4 × 95 sm | 1.6 | 2.3 | 43 | 5370 | 4 | 245 | 245 |
4 × 120 sm | 1.6 | 2.4 | 47 | 6563 | 3 | 285 | 285 |
4 × 150 sm | 1.8 | 2.6 | 51 | 7938 | 3 | 315 | 325 |
4 × 185 sm | 2.0 | 2.8 | 56 | 9756 | 3 | 355 | 370 |
4 × 240 sm | 2.2 | 3.0 | 62 | 12409 | 3 | 415 | 435 |
4 × 300 sm | 2.4 | 3.2 | 68 | 15104 | 3 | 465 | 500 |
5 × 10 re | 1.0 | 1.8 | 23.5 | 1305 | 7 | 69 | 60 |
5 × 10 rm | 1.0 | 1.8 | 24.1 | 1323 | 6 | 69 | 60 |
5 ×16 rm | 1.0 | 1.8 | 26.8 | 1750 | 5 | 89 | 80 |
5 × 25 rm | 1.2 | 1.9 | 31.3 | 2519 | 5 | 116 | 105 |
5 × 35 rm | 1.2 | 2.0 | 34.7 | 3158 | 4 | 138 | 130 |
5 × 50 rm | 1.4 | 2.1 | 39.7 | 4117 | 4 | 165 | 160 |
Մալուխի կառուցվածքը
● Conductor: [re] round solid conductor
[rm] circular stranded conductor
[Sm]Sector shape conductor
● Insulation: XLPE
● Filler:PVC
● Armour:A layers of Galvanized flat steel wires 4×0.8 mm with a counter helix layer of galvanized steel tape
● Out Sheath: PVC or FR-PVC type ST1/ST2/ST8,black
Կոդի նշանակում
NYFGBY
Դիմում
The NYFGBY cable is suitable for installation in the ground,indoors or on cable trunking where increased mechanical protection is required due to harsh operating condition.
Ստանդարտ
European standards:IEC 60502-1,VDE 0271,IS 1516.1
Flame retardant according to EN 60332-1
Indonesia standards:Conductor SNI IEC 60228/PVC insulation SNI IEC 60502-1/
PVC Sheath grade ST1 to SNI IEC 60502-1
Տեխնիկական տվյալները
Rated voltage:U0/U 0.6/1 kV
Test Voltage:3.5kV
Temperature Rating Maximum Operating: +70℃
Maximum Short-Circuit:+160℃
Minimum. Bend Radius:12×overall diameter
Վկայականներ
CE, RoHS, CCC, KEMA և այլ խնդրանքով