Parameter
No.cores × cross sec. |
AVG. Insulation Thickness |
AVG.Jacket (Sheath) Thickness |
Approx. O.D. | Approx. Weight | Conductor Resistance at 20°C |
mm² | mm | mm | mm | kg/km | Ω/km |
2×2.5 | 0.7 | 0.8 | 5.0±0.1×10.6±0.1 | 100 | 8.21 |
2×4 | 0.8 | 0.9 | 6.2±0.1×13.8±0.1 | 143 | 5.09 |
2×6 | 0.8 | 1 | 7.2±0.1×15.3±0.1 | 194 | 3.39 |
2×10 | 1 | 1 | 9.0±0.1×19.2±0.1 | 320 | 1.95 |
Cable Structure
Bare copper, tinned, finely stranded according
to IEC 60228 cl. 5
Double-insulated
Insulation cross-linked Polyolefin
Outer sheath cross-linked Polyolefin
Sheath colour black, red or blue
Properties
Ozone resistant acc. to EN 50396
• Weather and UV resistant acc. to HD 605/A1
• Halogen-free acc. to EN 50267-2-1,
EN 60684-2
• Resistant to acid and bases acc. to
EN 60811-2-1
Flame-resistant acc. to VDE 0482-332-1-2,
DIN EN 60332-1-2, IEC 60332-1
• Very robust and abraison-resistant sheath
acc. to DiN EN 53516
• Resistant to short-circuits up to 200'C thanks
to their double insulation; short-circuits
temperature 200'C/5 sec.
• Hydrolysis and ammoniac resistant
Application
Twin core PV cable is permitted to be installed in cable trays, wireways, conduits, etc. This cable meet the Varying needs of the Solar Industry.
Applications include cable routings from module strings to collect boxes and other required routings in balance of system integration.
Technical Data
• Temperature range
-40℃ to +90 ℃
Max. temp. at conductor +120C
• Nominal voltage
According to VDE U,/U 600/1000 V AC
1800 V DC conductor/conductor
• AC test voltage
10000 V
• Minimum bending radius
foued installation approx. 8 x outer diameters
flexóing 10 × cable diameter
Standard
TŨV (2 PfG 1169/08.2007, R60025298)RoHS complant