Parameter
Nom.Cross-section Area | Nominal Thickness Insulation | Approx.Twisted Diameter | cable Weight | Max.Conductor Resistance at 20°C | Current Carrying Capacity at 35°℃ |
mm² | mm | mm | km/kg | Ω/km | A |
NF2X | |||||
2×6mm | 1.2 | 13.0 | 136 | 3.080 | 54 |
2×10mm | 1.2 | 14.0 | 211 | 1.830 | 73 |
2×16mm | 1.2 | 16.0 | 334 | 1.150 | 97 |
4×6mm | 1.2 | 15.7 | 258 | 3.080 | 54 |
4×10mm | 1.2 | 17.0 | 422 | 1.830 | 73 |
4×16mm | 1.2 | 19.0 | 664 | 1.150 | 97 |
4×25mm | 1.4 | 24.0 | 1008 | 0.727 | 133 |
NFA2X | |||||
2×10mm | 1.2 | 14.0 | 94 | 3.080 | 54 |
2×16mm | 1.2 | 16.0 | 138 | 1.910 | 72 |
4×10mm | 1.2 | 17.0 | 187 | 3.080 | 54 |
4×16mm | 1.2 | 19.0 | 272 | 1.910 | 72 |
4×25mm | 1.4 | 24.0 | 423 | 1200 | 102 |
4×35mm | 1.6 | 27.0 | 564 | 0.868 | 125 |
Cable Structure
1 Conductor:
NF2X:Stranded Copper Conductor
NFA2X:Stranded All Aluminium Conductor (AAC)
2 Insulation:
Extrude of XLPE
Technical data
Nominal voltage:U0/U=0,6/1kV
Test voltage:3.5kV
Temperature range:during installation:-5℃
operating temperature:-30℃ up to +90℃
at short circuit of max.5 s:250℃
Minimum Bendig Radius 12×overall diameter
Standard
European standard:HD 626 S1,VDE 0276-626
Indonesia Standard:SPLN D3.010-1;2014,SPLN 42-10,SNI 04-1906:1990
(Other specidications are availiable upon request)
Certificates
CE,CCC,RoHS,KEMA and more others at request.