CABLE STRUCTURE:
Conductor: Plain circular solid copper conductor, conform to IEC 60228 class 1Plain circular stranded copper conductor, conform to IEC 60228 class 2
Insulation: PVC/C
Overall Sheath: PVC type ST4
Technical Data Voltage Rating Uo/U: 300/500V
Test Voltage -AC: 2kV
Temperature Rating: Flexible: -5℃ to +70℃
Fixed: -40℃ to+70℃
Minimum Bending Radius: Single Core: 7.5×overall diameter
Multicore: 4x overall diameter
| Nom.Cross- section Area | Conductor Type | Insulation Thickness | Inner covering Thickness | Sheath Thickness | Approx.O.D | Insulation Min Resistance at 90℃ | Max.D.C Resistance of Conductor (20℃) | |
| Lower Limit | Upper Limit | |||||||
| mm² | mm | mm | mm | mm | mm | MΩ/km | Ω/km | |
| 2×1.5 | 1 | 0.7 | 0.4 | 1.2 | 7.6 | 10 | 0.011 | 12.1 |
| 2×1.5 | 2 | 0.7 | 0.4 | 1.2 | 7.8 | 10.5 | 0.01 | 12.1 |
| 2×2.5 | 1 | 0.8 | 0.4 | 1.2 | 8.6 | 11.5 | 0.01 | 7.41 |
| 2×2.5 | 2 | 0.8 | 0.4 | 1.2 | 9 | 12 | 0.009 | 7.41 |
| 2×4 | 1 | 0.8 | 0.4 | 1.2 | 9.6 | 12.5 | 0.0085 | 4.61 |
| 2×4 | 2 | 0.8 | 0.4 | 1.2 | 10 | 13 | 0.0077 | 4.61 |
| 2×6 | 1 | 0.8 | 0.4 | 1.2 | 10.5 | 13.5 | 0.007 | 3.08 |
| 2×6 | 2 | 0.8 | 0.4 | 1.2 | 11 | 14 | 0.0065 | 3.08 |
| 2×10 | 1 | 1 | 0.6 | 1.4 | 13 | 16.5 | 0.007 | 1.83 |
| 2×10 | 2 | 1 | 0.6 | 1.4 | 13.5 | 17.5 | 0.0065 | 1.83 |
| 2×16 | 2 | 1 | 0.6 | 1.4 | 15.5 | 20 | 0.0052 | 1.15 |
| 2×25 | 2 | 1.2 | 0.8 | 1.4 | 18.5 | 24 | 0.005 | 0.727 |
| 2×35 | 2 | 1.2 | 1 | 1.6 | 21 | 27.5 | 0.0044 | 0.524 |
| 3×1.5 | 1 | 0.7 | 0.4 | 1.2 | 8 | 10.5 | 0.011 | 12.1 |
| 3×15 | 2 | 0.7 | 0.4 | 1.2 | 8.2 | 11 | 0.01 | 12.1 |
| 3×2.5 | 1 | 0.8 | 0.4 | 1.2 | 9.2 | 12 | 0.01 | 7.41 |
| 3×2.5 | 2 | 0.8 | 0.4 | 1.2 | 9.4 | 12.5 | 0.009 | 7.41 |
| 3×4 | 1 | 0.8 | 0.4 | 1.2 | 9.6 | 13 | 0.0085 | 4.61 |
| 3×4 | 2 | 0.8 | 0.4 | 1.2 | 10 | 13.5 | 0.0077 | 4.61 |
| 3×6 | 1 | 0.8 | 0.4 | 1.2 | 10.5 | 14.5 | 0.007 | 3.08 |
| 3×6 | 2 | 0.8 | 0.4 | 1.2 | 11.5 | 15.5 | 0.0065 | 3.08 |
| 3×10 | 1 | 1 | 0.6 | 1.4 | 12 | 17.5 | 0.007 | 1.83 |
| 3×10 | 2 | 1 | 0.6 | 1.4 | 14 | 19 | 0.0065 | 1.83 |
| 3×16 | 2 | 1 | 0.6 | 1.4 | 16.5 | 21.5 | 0.0052 | 1.15 |
| 3×25 | 2 | 1.2 | 0.8 | 1.4 | 20.5 | 26 | 0.005 | 0.727 |
| 3×35 | 2 | 1.2 | 1 | 1.6 | 22 | 29 | 0.0044 | 0.524 |
| 4×1.5 | 1 | 0.7 | 0.4 | 1.2 | 8.6 | 11.5 | 0.011 | 12.1 |
| 4×1.5 | 2 | 0.7 | 0.4 | 1.2 | 9 | 12 | 0.01 | 12.1 |
| 4×2.5 | 1 | 0.8 | 0.4 | 1.2 | 10 | 13 | 0.01 | 7.41 |
| 4×2.5 | 2 | 0.8 | 0.4 | 1.2 | 10 | 13.5 | 0.009 | 7.41 |
| 4×4 | 1 | 0.8 | 0.4 | 1.4 | 11.5 | 14.5 | 0.0085 | 4.61 |
| 4×4 | 2 | 0.8 | 0.4 | 1.4 | 12 | 15 | 0.0077 | 4.61 |
| 4×6 | 1 | 0.8 | 0.6 | 1.4 | 12.5 | 16 | 0.007 | 3.08 |
| 4×6 | 2 | 0.8 | 0.6 | 1.4 | 13 | 17 | 0.0065 | 3.08 |
| 4×10 | 1 | 1 | 0.6 | 1.4 | 15.5 | 19 | 0.007 | 1.83 |
| 4×10 | 2 | 1 | 0.6 | 1.4 | 16 | 20.5 | 0.0065 | 1.83 |
| 4×16 | 2 | 1 | 0.8 | 1.4 | 18 | 23.5 | 0.0052 | 1.15 |
| 4×25 | 2 | 1.2 | 1 | 1.6 | 22.5 | 28.5 | 0.005 | 0.727 |
| 4×35 | 2 | 1.2 | 1 | 1.6 | 24.5 | 32 | 0.0044 | 0.524 |
| 5×1.5 | 1 | 0.7 | 0.4 | 1.2 | 9.4 | 12 | 0.011 | 12.1 |
| 5×1.5 | 2 | 0.7 | 0.4 | 1.2 | 9.8 | 12.5 | 0.01 | 12.1 |
| 5×2.5 | 1 | 0.8 | 0.4 | 1.2 | 11 | 14 | 0.01 | 7.41 |
| 5×2.5 | 2 | 0.8 | 0.4 | 1.2 | 11 | 14.5 | 0.009 | 7.41 |
| 5×4 | 1 | 0.8 | 0.6 | 1.4 | 12.5 | 16 | 0.0085 | 4.61 |
| 5×4 | 2 | 0.8 | 0.6 | 1.4 | 13 | 17 | 0.0077 | 4.61 |
| 5×6 | 1 | 0.8 | 0.6 | 1.4 | 13.5 | 17.5 | 0.007 | 3.08 |
| 5×6 | 2 | 0.8 | 0.6 | 1.4 | 14.5 | 18.5 | 0.0065 | 3.08 |
| 5×10 | 1 | 1 | 0.6 | 1.4 | 17 | 21 | 0.007 | 1.83 |
Application For fixed electrical installations, laying the cable in wiring channels, as well as for electrical power distribution in electricity supply networks. Used as fixed wiring cable of rated voltage 300/500V.

At TianHuan Cable Group, we specialise in creating custom cables and harnesses for the world’s most demanding applications. Different materials are used according to customer requirements to meet different weather resistance, application, safety levels, and environmental requirements.