CABLE STRUCTURE:

Conductor:Stranded compacted conductor(copper or aluminum)

Semi-conductive conductor screen:Extruded cross-linked compound

Insulation:XLPE

Semi-conductive insulation screen:Extruded hand strippable semi-conductive cross-linked compound

Metallic screen:Copper wire screen(nominal 10kA for 1 second)

Outer sheath:PVC.Optional:HDPE,halogen-free,flame-retardant,plus termite protection(nylon,double brass tape or chemical additive).

Technical Data

Rated volatge:19/33 kV

Temperature range:Minimum installation temperature:0℃

Maximum operating temperature:+90℃

Minimum operating temperature:-25℃

Fault level:Up to 10kA for 1 sec

Bending radius:Installed cables:12D(PVC)  15D(HDPE)

During installation:18D(PVC)25D(HDPE)

Nominal conductor
area
Nominal insulation
thickness
Diameter
over insulation
Number of screen wires and diameter of screen wiresOverall DiameterApprox.
weight
Maximum pulling tensionMinimum Bending Radius
During installation
Minimum Bending Radius
Installed
mm2mmmmnb x mm ømmkg/kmkNmmmm
3×508.0 25.5 19/0.8563.3 3550 7.5 1230 820 
3×708.0 27.0 27/0.8566.5 4150 11 1310 870 
3×958.0 28.6 36/0.8570.0 4800 14 1380 920 
3×1208.0 30.2 40/0.8573.5 5250 18 1440 960 
3×1508.0 31.5 40/0.8576.3 5800 23 1500 1000 
3×1858.0 33.3 40/0.8580.1 6350 25 1570 1050 
3×2408.0 35.5 40/0.8584.9 7300 25 1670 1110 
3×3008.0 37.7 40/0.8589.7 8200 25 1750 1170 
3×4008.0 40.8 40/0.8596.4 9550 25 1870 1250 
3×5008.0 44.0 40/0.85103.3 11200 25 2130 1420 


Nominal conductor
area
Max. conductor DC resistance at 20℃Conductor AC resistance at 50Hz and 90℃Inductive reactance at 50Hz and 90℃Min insulation resistance at 20℃Current rating at core temp. 90℃ in groundCurrent rating at core temp. 90℃ in air
mm2Ohm/kmOhm/kmOhm/kmMOhm/kmAA
3×500.641 0.822 0.143 18000 158158
3×700.443 0.570 0.135 16000 194197
3×950.320 0.411 0.125 15000 231238
3×1200.253 0.325 0.124 13000 263273
3×1500.206 0.265 0.120 12000 295309
3×1850.164 0.211 0.113 11000 334354
3×2400.125 0.161 0.108 10000 387416
3×3000.100 0.130 0.106 9600 437475
3×4000.0778 0.102 0.0995 8700 501552
3×5000.0617 0.082 0.0969 7700 557616



Application

Distribution network cables serve as primary power supply for commercial,industrial and urban residential networks,suitable for high fault level systems (up to 10kA/1sec);higher fault current rated versions are available on request.Cu(Al) 19/33 kV-Three Core Heavy Duty Screened Unarmoured MV CABLE