CABLE STRUCTURE:
Conductor:Stranded compacted conductor(copper or aluminum)
Semi-conductive conductor screen:Extruded cross-linked compound
Insulation:XLPE
Semi-conductive insulation screen:Extruded hand strippable semi-conductive
cross-linked compound
Metallic screen:Copper wire screen(nominal 10kA for 1 second)
Outer sheath:PVC.Optional:HDPE,halogen-free,flame-retardant,plus termite protection(nylon,double brass tape or chemical additive)
Technical Data Rated volatge:19/33 kV
Temperature range:Minimum installation temperature:0℃
Maximum operating temperature:+90℃
Minimum operating temperature:-25℃
Fault level:Up to 10kA for 1 sec
Bending radius:Installed cables:12D(PVC only) 15D(HDPE)
During installation:18D(PVC only)
| Nominal conductor area | Nominal insulation thickness | Diameter over insulation | Number of screen wires and diameter of screen wires | Overall Diameter | Approx. weight | Maximum pulling tension | Minimum Bending Radius During installation | Minimum Bending Radius Installed |
| mm2 | mm | mm | nb x mm ø | mm | kg/km | kN | mm | mm |
| 1×50 | 8 | 25.5 | 34/1.35 | 34.3 | 1700 | 3.5 | 620 | 410 |
| 1×70 | 8 | 27 | 48/1.35 | 36 | 2100 | 4.9 | 650 | 430 |
| 1×95 | 8 | 28.6 | 48/1.35 | 37.6 | 2400 | 6.7 | 680 | 460 |
| 1×120 | 8 | 30.2 | 48/1.35 | 39.4 | 2700 | 8.4 | 710 | 470 |
| 1×150 | 8 | 31.5 | 48/1.35 | 40.7 | 3000 | 11 | 740 | 490 |
| 1×185 | 8 | 33.3 | 48/1.35 | 42.8 | 3400 | 13 | 770 | 510 |
| 1×240 | 8 | 35.5 | 48/1.35 | 45.2 | 4000 | 17 | 810 | 540 |
| 1×300 | 8 | 37.7 | 48/1.35 | 47.6 | 4650 | 21 | 850 | 570 |
| 1×400 | 8 | 40.8 | 48/1.35 | 50.9 | 5500 | 25 | 910 | 600 |
| 1×500 | 8 | 44 | 48/1.35 | 54.3 | 6793 | 25 | 980 | 650 |
| 1×630 | 8 | 47.9 | 48/1.35 | 58.4 | 8223 | 25 | 1050 | 700 |
Application Cables for electricity distribution networks are commonly employed as the main power supply for commercial,industrial,and urban residential grids.They are suitable for high fault-level systems with a rating of up to 10kA/1sec.

At TianHuan Cable Group, we specialise in creating custom cables and harnesses for the world’s most demanding applications. Different materials are used according to customer requirements to meet different weather resistance, application, safety levels, and environmental requirements.