The Standard
The Standard
Cu(Al)  12.7/22 kV-Three Core  Triplex Heavy Duty Screened  Unarmoured MV CABLE

Cu(Al) 12.7/22 kV-Three Core Triplex Heavy Duty Screened Unarmoured MV CABLE

CABLE STRUCTURE:

Conductor:Stranded compacted conductor(copper or aluminum)

Semi-conductive conductor screen:Extruded cross-linked compound

Insulation:XLPE

Semi-conductive insulation screen:Extruded hand strippable semi-conductive cross-linked compound

Metallic screen:Copper wire screen(nominal 10kA for 1 second)

Waterproof layer:Water blocking taped

Outer sheath:HDPE

Technical Data

Rated volatge:12.7/22 kV

Temperature range:Minimum installation temperature:0℃

Maximum operating temperature:+90℃

Fault level:Up to 10kA for 1 sec

Bending radius:Installed cables:15D(HDPE)

During installation:25D(HDPE)

Physical Character Sheet (AL Conductor)

Nominal conductor
area
Nominal insulation
thickness
Diameter
over insulation
Number of screen wires and diameter of screen wiresApprox.
overall
diameter
Approx.
weight
Maximum pulling tensionMinimum Bending Radius
Cable bundle
During installation
Minimum Bending Radius
Cable bundle
Installed
mm2mmmmnb x mm ømmkg/kmkNmmmm
3×505.5 20.523/1.3564.8 2950 7.5 940 630 
3×705.5 2232/1.3568.1 3610 11 1000 670 
3×955.5 23.643/1.3572.0 4440 14 1060 700 
3×1205.5 25.248/1.5375.4 4980 18 1110 740 
3×1505.5 26.548/1.5378.7 5360 23 1150 770 
3×1855.5 28.348/1.5382.6 5830 25 1210 810 
3×2405.5 30.548/1.5387.8 6500 25 1290 860 
3×3005.5 32.748/1.5393.0 7230 25 1320 910 
3×4005.5 35.848/1.53100.2 8290 25 1480 980 
3×5005.5 3948/1.53107.5 9520 25 1590 1060 

Electrical Data Sheet (AL Conductor)

Nominal conductor
area
Max. conductor DC resistance at 20℃Conductor AC resistance at 50Hz and 90℃Inductive reactance at 50Hz and 90℃Min insulation resistance at 20℃Current rating at core temp. 90℃ in groundCurrent rating at core temp. 90℃ in air
mm2Ohm/kmOhm/kmOhm/kmMOhm/kmAA
3×500.641 0.821 0.144 14000 158159
3×700.443 0.567 0.133 13000 191196
3×950.320 0.409 0.126 11000 227237
3×1200.253 0.324 0.122 10000 257271
3×1500.206 0.263 0.118 9700 287307
3×1850.164 0.210 0.115 9000 317344
3×2400.125 0.161 0.110 8100 372411
3×3000.100 0.128 0.107 7400 418169
3×4000.0778 0.102 0.103 6700 476546
3×5000.0619 0.0814 0.099 5900 538680

Physical Character Sheet (CU Conductor)

Nominal conductor
area
Nominal insulation
thickness
Diameter
over insulation
Number of screen wires and diameter of screen wiresApprox.
overall
diameter
Approx.
weight
Maximum pulling tensionMinimum Bending Radius
Cable bundle
During installation
Minimum Bending Radius
Cable bundle
Installed
mm2mmmmnb x mm ømmkg/kmkNmmmm
3×355.5 19.2   24/1.3561.632507.4 860 570 
3×505.5 20.5   34/1.3564.8 4230 11 920 610 
3×705.5 2248/1.3568.1 5500 15 1000 670 
3×955.5 23.6 48/1.3572620020 1040 690 
3×1205.5 25.2 48/1.3575.4 7160 25 1090 730 
3×1505.5 26.548/1.3578.7 8070 25 1140 760 
3×1855.5 28.3 48/1.3582.6 9250 25 1200 800 
3×2405.5 30.548/1.3587.81080025 1280 850 
3×3005.5 32.7 48/1.3593.0 12750 25 1350 900 
3×4005.5 35.8 48/1.35100.2 1540025 1450 970 
3×5005.5 3948/1.35107.51860025 1590 1060 

Electricial Data Sheet (CU Condutor)

Nominal conductor
area
Max. conductor DC resistance at 20℃Conductor AC resistance at 50Hz and 90℃Inductive reactance at 50Hz and 90℃Min insulation resistance at 20℃Current rating at core temp. 90℃ in groundCurrent rating at core temp. 90℃ in air
mm2Ohm/kmOhm/kmOhm/kmMOhm/kmAA
3×350.5240.6680.13911000145135
3×500.3870.4940.13210000172165
3×700.2680.3420.1238300209202
3×950.1930.2470.1177800252248
3×1200.1530.1960.1136800285282
3×1500.1240.1590.1176300318315
3×1850.0990.1280.1145700357354
3×2400.0750.0980.1095200408408
3×3000.060.0790.1064700467478
3×4000.0470.0630.1024200524539
3×5000.0370.0510.0993900581602


Application

Triplex cables are mainly used in medium-voltage power distribution,either overhead or underground.They carry power from substations to industrial sites,commercial buildings or homes,and their compact3-conductor design helps save space and ensure reliable power supply at the stated voltage.

Cu(Al)  12.7/22 kV-Three Core  Triplex Heavy Duty Screened  Unarmoured MV CABLE

The list of products in our website is continually being updated. Please send us an email if you have any questions about products that are not included yet.
Customized Service

At TianHuan Cable Group, we specialise in creating custom cables and harnesses for the world’s most demanding applications. Different materials are used according to customer requirements to meet different weather resistance, application, safety levels, and environmental requirements.

Contact Us +