پیرامیٹر
Nom.Cross-section Area | Nominal Thickness | overall diameter | cable Weight | DC Resistance at 20℃Insulation min | Current Carrying Capacity at 30℃ | ||
موصلیت | Outer Sheath | In Air | In Ground | ||||
mm² | mm² | ملی میٹر | ملی میٹر | km/kg | M.Ω.km | A | A |
2 × 25 rm | 1.2 | 1.8 | 24.9 | 1383 | 5 | 134 | 120 |
2 × 35 rm | 1.2 | 1.8 | 27.1 | 1709 | 4 | 160 | 150 |
2 × 50 rm | 1.4 | 1.9 | 30.5 | 2170 | 4 | 187 | 180 |
2 × 70 rm | 1.4 | 2.0 | 34.5 | 2846 | 4 | 230 | 230 |
2 × 95 rm | 1.6 | 2.1 | 39.2 | 3702 | 4 | 280 | 275 |
2 ×120 rm | 1.6 | 2.2 | 42.5 | 4423 | 3 | 320 | 320 |
2 ×150 rm | 1.8 | 2.3 | 46.9 | 5347 | 3 | 355 | 379 |
2 × 185 rm | 2.0 | 2.5 | 51.8 | 6501 | 3 | 409 | 430 |
2 × 240 rm | 2.2 | 2.7 | 58 | 8231 | 3 | 472 | 510 |
2 × 300 rm | 2.4 | 2.8 | 64.1 | 10081 | 3 | 525 | 590 |
3 × 16 rm | 1.0 | 1.8 | 22.6 | 1010 | 5 | 89 | 80 |
3 × 25 rm | 1.2 | 1.8 | 26.2 | 1695 | 5 | 116 | 105 |
3 × 35 rm | 1.2 | 1.8 | 28.6 | 2084 | 4 | 138 | 130 |
3 × 50 rm | 1.4 | 1.9 | 28.1 | 2403 | 4 | 165 | 160 |
3 × 70 rm | 1.4 | 2.0 | 31.3 | 3112 | 4 | 205 | 200 |
3 × 95 rm | 1.6 | 2.2 | 35.6 | 4151 | 4 | 245 | 245 |
3 × 120 rm | 1.6 | 2.3 | 38.4 | 5041 | 3 | 285 | 285 |
3 × 150 rm | 1.8 | 2.4 | 42.2 | 6121 | 3 | 315 | 325 |
3 × 185 rm | 2.0 | 2.6 | 46.8 | 7377 | 3 | 355 | 370 |
3 × 240 rm | 2.2 | 2.8 | 52.3 | 9536 | 3 | 415 | 435 |
3 × 300 rm | 2.4 | 3.0 | 57.4 | 11717 | 3 | 465 | 500 |
4 × 10 re | 1.0 | 1.8 | 22.2 | 1073 | 7 | 69 | 80 |
4 × 10 rm | 1.0 | 1.8 | 23 | 1101 | 6 | 69 | 80 |
4 × 16 rm | 1.0 | 1.8 | 26 | 1455 | 5 | 89 | 80 |
4 × 25 rm | 1.2 | 1.8 | 30 | 2093 | 5 | 116 | 105 |
4 × 35 rm | 1.2 | 1.9 | 33 | 2602 | 4 | 138 | 130 |
4 × 50 sm | 1.4 | 2.0 | 35 | 3080 | 4 | 165 | 160 |
4 × 70 sm | 1.4 | 2.1 | 38 | 4093 | 4 | 205 | 200 |
4 × 95 sm | 1.6 | 2.3 | 43 | 5370 | 4 | 245 | 245 |
4 × 120 sm | 1.6 | 2.4 | 47 | 6563 | 3 | 285 | 285 |
4 × 150 sm | 1.8 | 2.6 | 51 | 7938 | 3 | 315 | 325 |
4 × 185 sm | 2.0 | 2.8 | 56 | 9756 | 3 | 355 | 370 |
4 × 240 sm | 2.2 | 3.0 | 62 | 12409 | 3 | 415 | 435 |
4 × 300 sm | 2.4 | 3.2 | 68 | 15104 | 3 | 465 | 500 |
5 × 10 re | 1.0 | 1.8 | 23.5 | 1305 | 7 | 69 | 60 |
5 × 10 rm | 1.0 | 1.8 | 24.1 | 1323 | 6 | 69 | 60 |
5 ×16 rm | 1.0 | 1.8 | 26.8 | 1750 | 5 | 89 | 80 |
5 × 25 rm | 1.2 | 1.9 | 31.3 | 2519 | 5 | 116 | 105 |
5 × 35 rm | 1.2 | 2.0 | 34.7 | 3158 | 4 | 138 | 130 |
5 × 50 rm | 1.4 | 2.1 | 39.7 | 4117 | 4 | 165 | 160 |
کیبل کا ڈھانچہ
● Conductor: [re] round solid conductor
[rm] circular stranded conductor
[Sm]Sector shape conductor
● Insulation: XLPE
● Filler:PVC
● Armour:A layers of Galvanized flat steel wires 4×0.8 mm with a counter helix layer of galvanized steel tape
● Out Sheath: PVC or FR-PVC type ST1/ST2/ST8,black
کوڈ عہدہ
NYFGBY
درخواست
The NYFGBY cable is suitable for installation in the ground,indoors or on cable trunking where increased mechanical protection is required due to harsh operating condition.
معیاری
European standards:IEC 60502-1,VDE 0271,IS 1516.1
Flame retardant according to EN 60332-1
Indonesia standards:Conductor SNI IEC 60228/PVC insulation SNI IEC 60502-1/
PVC Sheath grade ST1 to SNI IEC 60502-1
تکنیکی ڈیٹا
Rated voltage:U0/U 0.6/1 kV
Test Voltage:3.5kV
Temperature Rating Maximum Operating: +70℃
Maximum Short-Circuit:+160℃
Minimum. Bend Radius:12×overall diameter
سرٹیفکیٹس
درخواست پر CE، RoHS، CCC، KEMA اور مزید دیگر