Parameter
Nom.Cross-section Area | Nominal Thickness Insulation | overall diameter | cable Weight | DC Resistance at 20℃Insulation min | Current Carrying Capacity at 30℃ in Air |
mm² os | mm | mm | km/kg | M.Ω.km | A |
1 × 50 rm | 1.0 | 10.8 | 151 | 900 | 204 |
1 × 70 rm | 1.1 | 12.7 | 214 | 900 | 257 |
1 × 95 rm | 1.1 | 14.6 | 288 | 800 | 316 |
1 × 120 rm | 1.2 | 16.3 | 362 | 800 | 368 |
1 × 150 rm | 1.4 | 18.3 | 451 | 800 | 421 |
1 × 185 rm | 1.6 | 20.5 | 566 | 800 | 488 |
1 × 240 rm | 1.7 | 23.3 | 736 | 700 | 583 |
1 × 300 rm | 1.8 | 25.7 | 907 | 700 | 675 |
1 × 400 rm | 2.0 | 29.1 | 1165 | 700 | 790 |
1 × 500 rm | 2.2 | 32.8 | 1490 | 700 | 921 |
1 × 630 rm | 2.4 | 37.1 | 1910 | 600 | 1091 |
Kab Kab
● Conductor: [rm] circular stranded conductor
● Insulation: XLPE
Txoj Cai Tsim
NA2XA
Daim ntawv thov
For Installations as underground,outdoor ,indoor,in ducts and where mechanical protection is required or for higher tensile stresses during installation and operation.
Txuj
Indonesia standards:Conductor SNI IEC 60228,SPLN 41-1,insulation SNI IEC 60502-1,SPLN 41-9
Technical Data
Rated voltage:U0/U 0.6/1 kV
Temperature Rating Maximum Operating: +90℃
Maximum Short-Circuit :+250℃
Minimum. Bending Radius:15×overall diameter
Daim ntawv pov thawj
CE, RoHS, CCC, KEMA thiab lwm yam ntawm kev thov