Parámetro
Type: NGA(BTLY) Specification: 1×10-1×500mm² Tensión nominal: 0,6/1KV | ||||||||
tabla 1 | ||||||||
Núcleo × área (mm²) |
Conductor diámetro (mm) |
Aislamiento espesor (mm) |
Espesor de aluminio conjunto de aleación (mm) |
Aprox. diámetro (mm) |
Aprox. peso (kg/km) |
Conductor resistencia Ω/km |
Que lleva capacidad A (laboral temperatura 90 ℃ y acostado el aire 40 ℃) |
Que lleva capacidad A (laboral temperatura 90 ℃ y suelo temperatura de 25℃) |
1×10 | 4.0 | 0.7 | 1.4 | 20.6 | 536.2 | 1.83 | 71 | 92 |
1×16 | 5.0 | 0.7 | 1.4 | 21.7 | 626.1 | 1.15 | 92 | 115 |
1×25 | 6.0 | 0.9 | 1.4 | 23.2 | 779.8 | 0.727 | 120 | 150 |
1×35 | 7.0 | 0.9 | 1.4 | 24.3 | 922.5 | 0.524 | 150 | 180 |
1×50 | 8.2 | 1.0 | 1.4 | 25.7 | 1088.6 | 0.387 | 180 | 215 |
1×70 | 9.9 | 1.1 | 1.4 | 27.9 | 1259.5 | 0.268 | 230 | 265 |
1×95 | 11.6 | 1.1 | 1.5 | 29.8 | 1498.6 | 0.193 | 285 | 320 |
1×120 | 13.0 | 1.2 | 1.5 | 31.6 | 1762.5 | 0.153 | 335 | 360 |
1×150 | 14.5 | 1.2 | 1.6 | 33.6 | 2109.3 | 0.124 | 385 | 410 |
1×185 | 16.2 | 1.3 | 1.6 | 35.9 | 2585.7 | 0.0991 | 450 | 460 |
1×240 | 18.4 | 1.3 | 1.7 | 38.8 | 3255.6 | 0.0754 | 535 | 535 |
1×300 | 20.7 | 1.3 | 1.8 | 40.6 | 3987.4 | 0.0601 | 620 | 605 |
Type: NGA(BTLY) Specification: 2×1.5-2×400mm² Tensión nominal: 0,6/1KV | ||||||||
Tabla 2 | ||||||||
Núcleo × área (mm²) |
Conductor diámetro (mm) |
Aislamiento espesor (mm) |
Espesor de aluminio conjunto de aleación (mm) |
Aprox. diámetro (mm) |
Aprox. peso (kg/km) |
Conductor resistencia (Ω/km) |
Que lleva capacidad A (laboral temperatura 90 ℃ y acostado el aire 40 ℃) |
Que lleva capacidad A (laboral temperatura 90 ℃ y suelo temperatura de 25℃) |
2×2.5 | 1.76 | 0.7 | 1.4 | 22.7 | 589.8 | 7.41 | 28 | 39 |
2×4 | 2.23 | 0.7 | 1.4 | 23.9 | 637.7 | 4.61 | 37 | 51 |
2×6 | 2.74 | 0.7 | 1.4 | 25.5 | 735.1 | 3.08 | 47 | 64 |
2×10 | 4.0 | 0.9 | 1.4 | 26.8 | 812.4 | 1.83 | 65 | 86 |
2×16 | 5.0 | 0.9 | 1.4 | 28.3 | 985.3 | 1.15 | 84 | 110 |
2×25 | 6.0 | 1.0 | 1.4 | 34.6 | 1106.5 | 0.727 | 110 | 140 |
2×35 | 7.0 | 1.1 | 1.5 | 35.8 | 1756.3 | 0.524 | 135 | 170 |
2×50 | 8.2 | 1.1 | 1.5 | 38.8 | 2012.6 | 0.387 | 170 | 205 |
2×70 | 9.9 | 1.1 | 1.6 | 42.2 | 2436.8 | 0.268 | 215 | 250 |
2×95 | 11.6 | 1.2 | 1.6 | 46.0 | 3098.6 | 0.193 | 265 | 300 |
2×120 | 13.0 | 1.2 | 1.6 | 49.1 | 3946.5 | 0.153 | 310 | 345 |
2×150 | 14.5 | 1.2 | 1.6 | 54.4 | 4589.3 | 0.124 | 350 | 385 |
2×185 | 16.2 | 1.3 | 1.8 | 59.4 | 5521.7 | 0.0991 | 405 | 435 |
2×240 | 18.4 | 1.3 | 1.8 | 64.8 | 6785.1 | 0.0754 | 480 | 500 |
2×300 | 20.7 | 1.3 | 1.8 | 68.1 | 8438.9 | 0.0601 | 555 | 565 |
Tipo: NGA(BTLY) Especificación: 3×1.5-3×400mm² Tensión nominal: 0,6/1KV | ||||||||
Tabla 3 | ||||||||
Núcleo × área (mm²) |
Conductor diámetro (mm) |
Aislamiento espesor (mm) |
Espesor de aluminio conjunto de aleación (mm) |
Aprox. diámetro (mm) |
Aprox. peso (kg/km) |
Conductor resistencia (Ω/km) |
Que lleva capacidad A (laboral temperatura 90 ℃ y acostado el aire 40 ℃) |
Que lleva capacidad A (laboral temperatura 90 ℃ y suelo temperatura de 25℃) |
3×2.5 | 1.76 | 0.7 | 1.4 | 26.5 | 683.5 | 7.41 | 28 | 39 |
3×4 | 2.23 | 0.7 | 1.4 | 27.9 | 812.1 | 4.61 | 37 | 51 |
3×6 | 2.74 | 0.7 | 1.4 | 29.3 | 930.2 | 3.08 | 47 | 64 |
3×10 | 4.0 | 0.9 | 1.4 | 30.4 | 1083.3 | 1.83 | 65 | 86 |
3×16 | 5.0 | 0.9 | 1.4 | 32.9 | 1359.6 | 1.15 | 84 | 110 |
3×25 | 6.0 | 1.0 | 1.4 | 33.8 | 2019.4 | 0.727 | 110 | 140 |
3×35 | 7.0 | 1.1 | 1.5 | 36.2 | 2511.2 | 0.524 | 135 | 170 |
3×50 | 8.2 | 1.1 | 1.5 | 39.8 | 3088.3 | 0.387 | 170 | 205 |
3×70 | 9.9 | 1.1 | 1.6 | 44.8 | 3954.6 | 0.268 | 215 | 250 |
3×95 | 11.6 | 1.2 | 1.6 | 48.7 | 4866.5 | 0.193 | 265 | 300 |
3×120 | 13.0 | 1.2 | 1.6 | 53.4 | 5798.3 | 0.153 | 310 | 345 |
3×150 | 14.5 | 1.2 | 1.6 | 58.2 | 6936.4 | 0.124 | 350 | 385 |
3×185 | 16.2 | 1.3 | 1.8 | 63.7 | 7832.6 | 0.0991 | 405 | 435 |
3×240 | 18.4 | 1.3 | 1.8 | 69.7 | 9155.8 | 0.0754 | 480 | 500 |
3×300 | 20.7 | 1.3 | 1.8 | 72.6 | 11264.2 | 0.0601 | 555 | 565 |
Tipo: NGA (BTLY) Especificación: 4 × 1,5-4 × 400 mm² Tensión nominal: 0,6/1KV | ||||||||
Tabla 4 | ||||||||
Núcleo × área (mm²) |
Conductor diámetro (mm) |
Aislamiento espesor (mm) |
Espesor de aluminio conjunto de aleación (mm) |
Aprox. diámetro (mm) |
Aprox. peso (kg/km) |
Conductor resistencia (Ω/km) |
Que lleva capacidad A (laboral temperatura 90 ℃ y acostado el aire 40 ℃) |
Que lleva capacidad A (laboral temperatura 90 ℃ y suelo temperatura de 25℃) |
4×2.5 | 1.76 | 0.7 | 1.4 | 27.9 | 694.4 | 7.41 | 28 | 39 |
4x4 | 2.23 | 0.7 | 1.4 | 29.3 | 773.1 | 4.61 | 37 | 51 |
4×6 | 2.74 | 0.7 | 1.4 | 30.4 | 929.3 | 3.08 | 47 | 64 |
4×10 | 4.0 | 0.9 | 1.4 | 32.9 | 1280 | 1.83 | 65 | 86 |
4×16 | 5.0 | 0.9 | 1.4 | 33.8 | 1687 | 1.15 | 84 | 110 |
4×25 | 6.0 | 1.0 | 1.4 | 36.2 | 2326.4 | 0.727 | 110 | 140 |
4×35 | 7.0 | 1.1 | 1.5 | 39.8 | 2937.9 | 0.524 | 135 | 170 |
4×50 | 8.2 | 1.1 | 1.5 | 44.8 | 3808.3 | 0.387 | 170 | 205 |
4×70 | 9.9 | 1.1 | 1.6 | 48.7 | 5205.2 | 0.268 | 215 | 250 |
4×95 | 11.6 | 1.2 | 1.6 | 53.4 | 6748.7 | 0.193 | 265 | 300 |
4×120 | 13.0 | 1.2 | 1.6 | 58.2 | 8225.6 | 0.153 | 310 | 345 |
4×150 | 14.5 | 1.2 | 1.6 | 63.7 | 9115.6 | 0.124 | 350 | 385 |
4×185 | 16.2 | 1.3 | 1.8 | 69.7 | 10076.2 | 0.0991 | 405 | 435 |
4×240 | 18.4 | 1.3 | 1.8 | 72.6 | 11717.4 | 0.0754 | 480 | 500 |
4×300 | 20.7 | 1.3 | 1.8 | 81.2 | 14444.8 | 0.0601 | 555 | 565 |
Tipo: NGA (BTLY) Especificación: 5 × 1,5-5 × 400 mm² Tensión nominal: 0,6/1KV | ||||||||
Tabla 5 | ||||||||
Núcleo × área (mm²) |
Conductor diámetro (mm) |
Aislamiento espesor (mm) |
Espesor de aluminio conjunto de aleación (mm) |
Aprox. diámetro (mm) |
Aprox. peso (kg/km) |
Conductor resistencia (Ω/km) |
Que lleva capacidad A (laboral temperatura 90 ℃ y acostado el aire 40 ℃) |
Que lleva capacidad A (laboral temperatura 90 ℃ y suelo temperatura de 25℃) |
5×2.5 | 1.76 | 0.7 | 1.4 | 30.0 | 856.4 | 7.41 | 28 | 39 |
5×4 | 2.23 | 0.7 | 1.4 | 33.2 | 929.3 | 4.61 | 37 | 51 |
5×6 | 2.74 | 0.7 | 1.4 | 35.0 | 1145.6 | 3.08 | 47 | 64 |
5×10 | 4.0 | 0.9 | 1.4 | 38.4 | 1549.1 | 1.83 | 65 | 86 |
5×16 | 5.0 | 0.9 | 1.4 | 42.6 | 1983.7 | 1.15 | 84 | 110 |
5×25 | 6.0 | 1.0 | 1.4 | 47.0 | 2937.9 | 0.727 | 110 | 140 |
5×35 | 7.0 | 1.1 | 1.5 | 51.2 | 3808.3 | 0.524 | 135 | 170 |
5×50 | 8.20 | 1.1 | 1.5 | 54.9 | 4608.6 | 0.387 | 170 | 205 |
5×70 | 9.90 | 1.1 | 1.6 | 60.1 | 5955.1 | 0.268 | 215 | 250 |
5×95 | 11.6 | 1.2 | 1.6 | 65.8 | 7269.2 | 0.193 | 265 | 300 |
5×120 | 13.0 | 1.2 | 1.6 | 68.6 | 8225.6 | 0.153 | 310 | 345 |
5×150 | 14.5 | 1.2 | 1.6 | 71.6 | 10076.2 | 0.124 | 350 | 385 |
5×185 | 16.2 | 1.3 | 1.8 | 75.9 | 12482.6 | 0.0991 | 405 | 435 |
5×240 | 18.4 | 1.3 | 1.8 | 76.5 | 15793.9 | 0.0754 | 480 | 500 |
5×300 | 20.7 | 1.3 | 1.8 | 83.7 | 19455.1 | 0.0601 | 555 | 565 |
Tipo: NGA(BTLY) Especificación: 3×4+1×2.5-3×400+1×185mm² Tensión nominal: 0,6/1KV | ||||||||||
Tabla 6 | ||||||||||
Núcleo × área (mm²) |
Conductor diámetro (mm) |
Aislamiento espesor (mm) |
Espesor de aluminio conjunto de aleación (mm) |
Aprox. diámetro (mm) |
Aprox. peso (kg/km) |
Conductor resistencia (Ω/km) |
Que lleva capacidad A (laboral temperatura 90 ℃ y acostado el aire 40 ℃) |
Que lleva capacidad A (laboral temperatura 90 ℃ y suelo temperatura de 25℃) |
||
Fase | Neutral | Fase | Neutral | |||||||
3×4+1×2,5 | 2.23 | 1.76 | 0.7 | 0.7 | 1.4 | 29.2 | 868.4 | 4.61 | 37 | 51 |
3×6+1×4 | 2.74 | 2.23 | 0.7 | 0.7 | 1.4 | 30.5 | 987.3 | 3.08 | 47 | 64 |
3×10+1×6 | 4.0 | 2.74 | 0.7 | 0.7 | 1.4 | 32.9 | 1126.3 | 1.83 | 65 | 86 |
3×16+1×10 | 5.0 | 4.0 | 0.7 | 0.7 | 1.4 | 34.8 | 1498.2 | 1.15 | 84 | 110 |
3×25+1×16 | 6.0 | 5.0 | 0.9 | 0.7 | 1.4 | 41.5 | 2468.7 | 0.727 | 110 | 140 |
3×35+1×16 | 7.0 | 5.0 | 0.9 | 0.7 | 1.4 | 43.6 | 2796.5 | 0.524 | 135 | 170 |
3×50+1×25 | 8.2 | 6.0 | 1.0 | 0.9 | 1.5 | 45.8 | 3469.1 | 0.387 | 170 | 205 |
3×70+1×35 | 9.9 | 7.0 | 1.1 | 0.9 | 1.5 | 49.6 | 4398.2 | 0.268 | 215 | 250 |
3×95+1×50 | 11.6 | 8.2 | 1.1 | 1.0 | 1.6 | 52.7 | 5477.3 | 0.193 | 265 | 300 |
3×120+1×70 | 13.0 | 9.9 | 1.2 | 1.1 | 1.6 | 57.6 | 6781.9 | 0.153 | 310 | 345 |
3×150+1×70 | 14.5 | 9.9 | 1.4 | 1.1 | 1.6 | 61.2 | 7988.4 | 0.124 | 350 | 385 |
3×185+1×95 | 16.2 | 11.6 | 1.6 | 1.1 | 1.8 | 64.9 | 9654.2 | 0.0991 | 405 | 435 |
3×240+1×120 | 18.4 | 13.0 | 1.7 | 1.2 | 1.8 | 69.4 | 11386.1 | 0.0754 | 480 | 500 |
3×300+1×150 | 20.7 | 14.5 | 1.8 | 1.4 | 1.8 | 75.8 | 13125.6 | 0.0601 | 555 | 565 |
Tipo: NGA (BTLY) Especificación: 3 × 4 + 2 × 2,5-3 × 400 + 2 × 185 mm² Tensión nominal:0,6/1KV | ||||||||||
Tabla 7 | ||||||||||
Núcleo × área (milímetros²) |
Conductor diámetro (mm) |
Aislamiento espesor (mm) |
Vaina Espesor (mm) |
Aprox. diámetro (mm) |
Aprox. peso (kg/km) |
Conductor resistencia (Ω/km) |
Que lleva capacidad A (laboral temperatura 90 ℃ y acostado el aire 40 ℃) |
Que lleva capacidad A (laboral temperatura 90 ℃ y suelo temperatura de 25℃) |
||
Fase | Neutral | Fase | Neutral | |||||||
3×4+2×2,5 | 2.23 | 1.76 | 0.7 | 0.7 | 1.4 | 31.2 | 917.2 | 4.61 | 37 | 51 |
3×6+2×4 | 2.74 | 2.23 | 0.7 | 0.7 | 1.4 | 32.3 | 1036.2 | 3.08 | 47 | 64 |
3×10+2×6 | 4.0 | 2.74 | 0.7 | 0.7 | 1.4 | 34.6 | 1321.6 | 1.83 | 65 | 86 |
3×16+2×10 | 5.0 | 4.0 | 0.7 | 0.7 | 1.4 | 36.1 | 1688.2 | 1.15 | 84 | 110 |
3×25+2×16 | 6.0 | 5.0 | 0.9 | 0.7 | 1.4 | 43.2 | 3102.4 | 0.727 | 110 | 140 |
3×35+2×16 | 7.0 | 5.0 | 0.9 | 0.7 | 1.4 | 44.8 | 3516.2 | 0.524 | 135 | 170 |
3×50+2×25 | 8.2 | 6.0 | 1.0 | 0.9 | 1.5 | 47.5 | 4328.5 | 0.387 | 170 | 205 |
3×70+2×35 | 9.9 | 7.0 | 1.1 | 0.9 | 1.5 | 50.4 | 5436.9 | 0.268 | 215 | 250 |
3×95+2×50 | 11.6 | 8.2 | 1.1 | 1.0 | 1.6 | 55.2 | 6784.7 | 0.193 | 265 | 300 |
3×120+2×70 | 13.0 | 9.9 | 1.2 | 1.1 | 1.6 | 59.1 | 8213.6 | 0.153 | 310 | 345 |
3×150+2×70 | 14.5 | 9.9 | 1.4 | 1.1 | 1.6 | 64.8 | 9238.7 | 0.124 | 350 | 385 |
3×185+2×95 | 16.2 | 11.6 | 1.6 | 1.1 | 1.8 | 68.9 | 10254.7 | 0.0991 | 405 | 435 |
3×240+2×120 | 18.4 | 13.0 | 1.7 | 1.2 | 1.8 | 74.5 | 13689.4 | 0.0754 | 480 | 500 |
3×300+2×150 | 20.7 | 14.5 | 1.8 | 1.4 | 1.8 | 80.1 | 16527.8 | 0.0601 | 555 | 565 |
Tipo: NGA(BTLY) Especificación: 4×4+1×2.5-4×400+1×185mm² Tensión nominal: 0,6/1KV | ||||||||||
Tabla 8 | ||||||||||
Núcleo × área (mm²) |
Conductor diámetro (mm) |
Aislamiento espesor (mm) |
Vaina Espesor (mm) |
Aprox. diámetro (mm) |
Aprox. peso (kg/km) |
Conductor resistencia (Ω/km) |
Que lleva capacidad A (laboral temperatura 90 ℃ y acostado el aire 40 ℃) |
Que lleva capacidad A (laboral temperatura 90 ℃ y suelo temperatura de 25℃) |
||
Fase | Neutral | Fase | Neutral | |||||||
4×4+1×2,5 | 2.23 | 1.76 | 0.7 | 0.7 | 1.8 | 30.8 | 971.2 | 4.61 | 37 | 51 |
4×6+1×4 | 2.74 | 2.23 | 0.7 | 0.7 | 1.8 | 31.7 | 1039.1 | 3.08 | 47 | 64 |
4×10+1×6 | 4.0 | 2.74 | 0.7 | 0.7 | 1.8 | 33.9 | 1354.1 | 1.83 | 65 | 86 |
4×16+1×10 | 5.0 | 4.0 | 0.7 | 0.7 | 1.8 | 36.1 | 1809.2 | 1.15 | 84 | 110 |
4×25+1×16 | 6.0 | 5.0 | 0.9 | 0.7 | 1.8 | 42.6 | 2440.1 | 0.727 | 110 | 140 |
4×35+1×16 | 7.0 | 5.0 | 0.9 | 0.7 | 1.8 | 45.1 | 2828.7 | 0.524 | 135 | 170 |
4×50+1×25 | 8.2 | 6.0 | 1.0 | 0.9 | 1.9 | 48.6 | 3730.2 | 0.387 | 170 | 205 |
4×70+1×35 | 9.9 | 7.0 | 1.1 | 0.9 | 2.1 | 52.9 | 4946.1 | 0.268 | 215 | 250 |
4×95+1×50 | 11.6 | 8.2 | 1.1 | 1.0 | 2.2 | 55.7 | 6382.6 | 0.193 | 265 | 300 |
4×120+1×70 | 13.0 | 9.9 | 1.2 | 1.1 | 2.4 | 60.8 | 8055.3 | 0.153 | 310 | 345 |
4×150+1×70 | 14.5 | 9.9 | 1.4 | 1.1 | 2.5 | 66.2 | 9238.7 | 0.124 | 350 | 385 |
4×185+1×95 | 16.2 | 11.6 | 1.6 | 1.1 | 2.7 | 70.5 | 11554.2 | 0.0991 | 405 | 435 |
4×240+1×120 | 18.4 | 13.0 | 1.7 | 1.2 | 2.9 | 76.8 | 14430.1 | 0.0754 | 480 | 500 |
4×300+1×150 | 20.7 | 14.5 | 1.8 | 1.4 | 3.1 | 81.2 | 17757.3 | 0.0601 | 555 | 565 |
Solicitud
El cable MI se utiliza principalmente para entornos de alta temperatura o sistemas de señal y energía críticos para la seguridad; sin embargo, también se puede utilizar dentro de un área alquilada, transportando electricidad suministrada y facturada al propietario.
Estructura de cables
1.Conductor de cobre
2.Capa de aislamiento
3.capa refractaria
4.Capa aislante
5.Funda de aluminio
6.Funda libre de halógenos con bajo nivel de humo
Aplicaciones
Este producto es adecuado para líneas con voltaje nominal de 0,6/1KV e inferior, y se usa ampliamente en plantas de energía nuclear, metalurgia, industria química, minas, hornos y otros entornos peligrosos, hostiles y de alta temperatura.
En los últimos años, también se ha utilizado en edificios de gran altura, aeropuertos, muelles, ferrocarriles subterráneos y otros lugares para garantizar el funcionamiento ininterrumpido de bombas contra incendios, ascensores contra incendios, iluminación local, instrucciones de evacuación de emergencia, monitoreo de seguridad, sistemas de prevención de humo y suministros de energía autoprovistos y otra electricidad de protección contra incendios y equipos importantes en caso de incendio.
Caracteristicas de producto
1) No es necesario usar un tubo separado al colocarlo, y tiene las mismas funciones a prueba de agua y de impacto que BTT.
2) La temperatura nominal máxima para los conductores de cable es 125 ℃
3) El producto se puede producir de 1 a 37 núcleos en especificaciones de 1,5 a 6 mm², de 1 a 5 núcleos en especificaciones de 10 a 240 mm² y de un solo núcleo en especificaciones de 300 a 630 mm².
4) El cable ha pasado las tres pruebas de C, W y E en BS6387, lo que puede mantener la integridad del circuito durante el incendio.
5)Buenas funciones anti-ratas, anti-hormigas y anti-radiación, que pueden garantizar la estabilidad, larga vida útil y durabilidad del cable.
6) Baja temperatura de funcionamiento, pequeña pérdida de línea, fuerte capacidad antisobrecarga, larga vida útil y alta seguridad, especialmente adecuado para aplicaciones en proyectos con requisitos de protección ambiental
7) Resistente a la corrosión (la funda metálica del cable con aislamiento mineral modelo BTLY es altamente resistente a la corrosión y, para la mayoría de las instalaciones, no requiere medidas de protección adicionales; incluso en lugares donde la funda metálica del cable es susceptible a la corrosión química o Contaminación industrial, sigue siendo seguro porque la capa más externa del cable está protegida por una funda exterior de plástico.
8) A prueba de explosiones (el material aislante altamente compactado en el cable y la terminación del cable instalada con un prensaestopas especial pueden evitar que vapor, gas y llamas entren en el equipo eléctrico conectado al cable, por lo que se usa en lugares con riesgo de explosión y la conexión de diversos equipos y equipos a prueba de explosiones.
9) Alta resistencia mecánica (el cable con aislamiento mineral BTLY es robusto y duradero, y aún puede funcionar normalmente cuando el diámetro del cable se deforma en un tercio, sus propiedades eléctricas no se dañarán incluso si se somete a daños mecánicos graves).